SAG582120600
System Application Guide
Revision BK, September 27, 2017
Spec. No. 582120600 (Model 801DB
NVGB
)
Page 56 of 75
5/16-18 swage studs
for installation of customer
provided single hole lugs.
(Torque to 132 in-lbs.)
(Maximum Lug Width is 1.800”.)
(Maximum Wire Size is 2/0 AWG.)
1/4-20 swage studs
for installation of customer
provided single hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.750”.)
(Maximum Wire Size is 2 AWG.)
-48V Load
Connections
-48V Load
Connections
Rear View
(wired from the rear of the bay)
1/4-20 studs on 5/8” centers for
installation of customer provided
two hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.610”.)
(Maximum Wire Size is 2 AWG.)
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
Ensure leads are connected to
proper polarity for the device
installed, either a Distribution
Device (load lead connection)
or a TVSS Device (ground
connection).
*
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
-48V Load Connections and
TVSS Device Ground Connections to
List 115 and 125 Distribution Panel
Rear View
(wired from the rear of the bay)
-48V Load Connections to
List 110 and 120 Distribution Panel