System Application Guide
SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB
)
Revision BK, September 27, 2017
Page 25 of 75
THESE LIST OPTIONS CANNOT BE USED IN THE
CURRENT DESIGN BAY (MODEL 801DB
NVGB
)
FOR MANUFACTURER DISCONTINUED BAYS (MODEL 1293V3)
Distribution Bus Module Paralleling Options
To Parallel This List
W
I
T
H
This List
Order
Paralleling
Option List
Purchased
Before 6/30/00
Purchased
After 6/30/00
Purchased
Before 6/30/00
Purchased
After 6/30/00
10, 11, 12, or 14
--
10, 11, 12, or 14
--
30, 35
20, 21, 22, or 24
--
20, 21, 22, or 24
--
31, 36
15
--
15
--
35 or 37
25
--
25
--
36 or 38
--
10, 11, 12, 14, or 15
--
10, 11, 12, 14, or 15
35 or 37
--
13
--
13
35 or 37
--
20, 20G, 21, 22, 24, or
25
--
20, 20G, 21, 22, 24, or
25
36 or 38
--
23
--
23
36 or 38
15
--
--
10, 11, 12, 14, or 15
35 or 37
25
--
--
20, 20G, 21, 22, 24, or
25
36 or 38
10, 11, 12,
or 14
--
--
10, 11, 12,
or 14
30*, 35
20, 21, 22,
or 24
--
--
20, 20G, 21, 22,
or 24
31*, 36
10, 11, 12, or 14
--
15
--
NONE
20, 21, 22, or 24
--
25
--
NONE
10, 11, 12, or 14
--
--
15
NONE
20, 21, 22, or 24
--
--
25
NONE
Notes: Total load for all paralleled distribution bus modules is limited to 640 amperes, maximum.
List 35 and 36 provide multiple load shunts.
List 30, 31, 37, and 38 provide a single load shunt.
*
Requires additional components,
see Lists 30 and 31 Ordering Notes
in Issue AR SAG582120600.