![Vertiv NetSure 801DB NVGB System Application Manual Download Page 62](http://html1.mh-extra.com/html/vertiv/netsure-801db-nvgb/netsure-801db-nvgb_system-application-manual_1008112062.webp)
SAG582120600
System Application Guide
Revision BK, September 27, 2017
Spec. No. 582120600 (Model 801DB
NVGB
)
Page 62 of 75
Optional List 148 2400A Ground/Return
Input Kit provides Additional DC Input
Connections (Battery Return Leads)
3/8” clearance holes on
1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 750 kcmil)
Top and Bottom Feed
3/8” clearance holes on
1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 750 kcmil)
List 148 Feed
Optional
bonding
strap (P/O
List 148)
can be
removed
if not
required.
Optional
bonding
strap (P/O
List 148)
can be
removed
if not
required.
Top Feed DC Input Connections
(Battery Return Leads)
Bottom Feed
DC Input Connections
(Battery Return Leads)
Optional List 148 2400A Ground/Return
Input Kit provides Additional DC Input
Connections (Battery Return Leads)
Optional List 116 Internal
Ground/Return Busbar
Arranged for Top Feed
(List 126 similar)
Optional List 116 Internal
Ground/Return Busbar
Arranged for Bottom Feed
(List 126 similar)
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.