FIELD
DESCRIPTION
Engine ID
Read-only display of engine ID.
Context Name
Alphanumeric name of the SNMP v3 interface.
User Name
Unique name for each user.
Access Mode
Selects mode of access for the user.
•
No-Auth - requires a user name, but not a password.
•
Auth-MD5 - requires a user name and password.
•
PrivAuth-MD5 - requires a user name and password.
Auth-Password
Sets the authentication password. 8 to 24 characters in length.
Priv-Password
Sets the privacy password. 8 to 24 characters in length.
Table 7.16 SnmpV3 options
Sending a Leak-detection Test Trap
1. Click
Configuration
>
SNMP/Syslog
.
on page 47 opens.
2. At the bottom of the page, click
Send Test Trap - Leak Detected
.
The test message is sent.
Sending a Cable-break Test Trap
1. Click
Configuration
>
SNMP/Syslog
.
on page 47 opens.
2. At the bottom of the page, click
Send Test Trap - Cable Break.
The test message is sent.
Sending a Contamination Test Trap
1. Click
Configuration
>
SNMP/Syslog
.
on page 47 opens.
2. At the bottom of the page, click
Send Test Trap - Contamination
.
The test message is sent.
5.3.13 EIA-485 Port/Modbus Configuration
Use this port-configuration page to set up the LP6000 controller as a Modbus "master" to communicate
with the "slave" devices through the EIA-485 or Ethernet ports. For slaved devices, use the web interface
of each slave to configure communication with the master LP6000 controller. See
on page 49 for the detailed set-up steps.
The page also sets-up access to BACnet-MS/TP slave devices and accesses the Modbus slave-register
log, statistics and packet log. See
Viewing the Modbus Slave-register Log
on page 49 and
NOTE: The options listed may differ from your screen depending on the port function selected.
Vertiv
| Liqui-tect LP6000 Installer/User Guide |
48
Summary of Contents for Liqui-tect LP6000
Page 1: ...Liqui tect LP6000 Leak detection System Leak detection System Installer User Guide...
Page 18: ...Vertiv Liqui tect LP6000 Installer User Guide 18 This page intentionally left blank...
Page 20: ...Vertiv Liqui tect LP6000 Installer User Guide 20 This page intentionally left blank...
Page 34: ...Vertiv Liqui tect LP6000 Installer User Guide 34 This page intentionally left blank...
Page 60: ...Vertiv Liqui tect LP6000 Installer User Guide 60 This page intentionally left blank...
Page 74: ...Vertiv Liqui tect LP6000 Installer User Guide 74 This page intentionally left blank...
Page 76: ...Vertiv Liqui tect LP6000 Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liqui tect LP6000 Installer User Guide 80 This page intentionally left blank...
Page 81: ......