24
Vertiv™ Liebert EXS 80kVA UPS User Manual
2 Mechanical Installation
2.6.4. Storage Environment
Should the UPS not be installed immediately, it must be stored with the original packaging in a
room for protection against excessive humidity and heat sources. The battery needs to be stored
in a dry and cool place with good ventilation. The most suitable storage temperature ranges from
20 °C to 25 °C.
WARNING! During the storage period, the battery must be charged at regular intervals, in
accordance with the battery instructions. When charging the battery, you can connect the UPS
to the mains temporarily to charge the battery and activate it.
2.7 Mechanical Requirements
2.7.1. Moving Cabinet
WARNING!
1. The lifting equipment for moving the UPS cabinet must have enough lift
capacity. Refer to Table 10-3 for its weight.
2. Due to its intensity, the castor may not be valid on the uneven surface.
3. The center of gravity of the UPS cabinet is high; avoid falling over during the cabinet
movement.
4. Vertical hanging of cabinet is not allowed.
5. During transportation and installation, the product tilt angle shanll not be greater than 15o..
Caution:
When carrying the UPS with batteries built-in, you must independently fasten
each battery string and keep the moving distance to a minimum.
2.7.2. Clearance
Because the UPS has no grille at the two sides, there is no special clearance requirement on the
two sides.
Besides the local regulations, to enable routine tightening of the power terminals within the UPS,
it is recommended that clearance around the front of the UPS should maintain a clearance at
least 1200mm. It is recommended that clearance around the rear of the UPS should maintain a
clearance at least 500mm.
2.7.3. Cable Access Mode
For further description, refer to
Summary of Contents for Liebert EXS 80kVA UPS
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Page 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Page 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Page 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Page 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Page 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...