Vertiv™ Liebert EXS 80kVA UPS User Manual
Appendix I LCD Parameters Setting
Menu
Item
Setting range
Default setting
Dry contact
Battery Capacity Setting
for Load Shed Signal 1
0~100%
0
Battery Backup Time
Setting for Load Shed
Signal 1
0~3600 Sec
0 Sec
Battery Capacity Setting
for Load Shed Signal 2
0~100%
0
Battery Backup Time
Setting for Load Shed
Signal 2
0~3600 Sec
0 Sec
General Purpose Dry
Contact J14-5/7(O)
N/A, Summary alarm, On battery, Low
Battery Alarm, UPS Fault, On Bypass,
On Inverter, Remote EPO Status, Input
Mains Failure, Maint. Bypass Switch
Closed, Load Shed Signal 1, Load Shed
Signal 2, Maint. Bypass Switch Interlock
N/A
General Purpose Dry
Contact J14-1/3(O)
N/A, Summary alarm, On battery, Low
Battery Alarm, UPS Fault, On Bypass,
On Inverter, Remote EPO Status, Input
Mains Failure, Maint. Bypass Switch
Closed, Load Shed Signal 1, Load Shed
Signal 2, Maint. Bypass Switch Interlock
N/A
General Purpose Dry
Contact J13-13(I)
N/A, onGen, Inhibit trans. to inverter,
Ext_MIB, Ext MBB status, MOB, Battery
GND Fault, Charger Off, Suspend ECO
mode, Start Battery Maint. Test, Stop
Battery Maint. Test, Alarm Reset
onGen
General Purpose Dry
Contact J13-2(I)
N/A, onGen, Inhibit trans. to inverter,
Ext_MIB, Ext MBB status, MOB, Battery
GND Fault, Charger Off, Suspend ECO
mode, Start Battery Maint. Test, Stop
Battery Maint. Test, Alarm Reset
Inhibit trans. to
inverter
General Purpose Dry
Contact J13-1(I)
N/A, onGen, Inhibit trans. to inverter,
Ext_MIB, Ext MBB status, MOB, Battery
GND Fault, Charger Off, Suspend ECO
mode, Start Battery Maint. Test, Stop
Battery Maint. Test, Alarm Reset
Ext_MIB
General Purpose Dry
Contact J13-9(I)
N/A, onGen, Inhibit trans. to inverter,
Ext_MIB, Ext MBB status, MOB, Battery
GND Fault, Charger Off, Suspend ECO
mode, Start Battery Maint. Test, Stop
Battery Maint. Test, Alarm Reset
Ext MBB status
General Purpose Dry
Contact J13-5(I)
N/A, onGen, Inhibit trans. to inverter,
Ext_MIB, Ext MBB status, MOB, Battery
GND Fault, Charger Off, Suspend ECO
mode, Start Battery Maint. Test, Stop
Battery Maint. Test, Alarm Reset
MOB
Summary of Contents for Liebert EXS 80kVA UPS
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Page 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Page 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Page 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Page 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Page 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...