17
Vertiv™ Liebert EXS 80kVA UPS User Manual
2 Mechanical Installation
2 Mechanical Installation
This chapter briefly introduces the mechanical installation of the UPS, including the precautions, initial
inspection before installation, environmental requirement, mechanical requirement and installation
diagram.
2.1 Precautions
No two sites are the same, therefore this section provides general guidelines, procedures and methods for
installation engineers, who shall adapt the installation to meet the actual conditions.
WARNING! Professional installation required
1. The UPS should be installed by a qualified engineer in accordance with the information
provided in this section. In the event of any problems, contact your local Vertiv service center
immediately.
2. The UPS must NOT be switched on without the approval of the commissioning engineer.
3. In the case of any equipment or items not covered by this section, refer to the specific
mechanical and/or electrical installation instructions provided with such items.
WARNING! The UPS can be connected to IT (4-pole CB should be configured at upatream), TN
and TT AC distribution systems (IEC60364-3), and must be of 3-phase 5-wire (A, B, C, N, PE)
system.
WARNING! Battery danger
Take special care when installing batteries. When connecting batteries, the battery terminal
generates DC high voltage, which is fatal to human being.
1. Please wear safety glasses to protect the eyes from being damaged by arc.
2. Remove all the metal items, including finger rings, watch, etc.
3. Use tools with insulated handle.
4. Wear rubber gloves.
5. If the battery has electrolyte leakage or the battery is damaged, it must be replaced. Place
the battery into the container that can withstand sulfuric acid and dispose of it according to the
local regulations.
6. If the skin contacts the electrolyte, flush it with water immediately.
Summary of Contents for Liebert EXS 80kVA UPS
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Page 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Page 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Page 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Page 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Page 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...