48
Vertiv™ Liebert EXS 80kVA UPS User Manual
4 Operator Control And Display Panel
Fault
Meaning
Bypass Input Breaker Open
The bypass switch is opened
System Interrupt Transfer
Execute the interval transfer under conditions of bypass unable to trace and inverter
phase not locked
LBS Active
LBS is enabled
Module in Sleeping
The module is in sleep mode and the module does not work. Only the UPS configured with
intelligent parallel mode or intelligent ECO demo mode can present this state
Module Comms. Normal
Communication between the module and monitoring is normal
ECO Mode Enabled
ECO mode enabled
ECO Mode Active
ECO mode activated
Freq. Converter Mode Enabled
Frequency converter mode enabled
Freq. Converter Mode Active
Frequency converter mode activated
IP Mode Enabled
Intelligent parallel mode enabled, that is sleep mode
IP Mode Active
Intelligent parallel mode activated, that is sleep mode
IP Mode Demo Enabled
Intelligent parallel demo mode enabled, that is sleep demo mode
IP Mode Demo Active
Intelligent parallel demo mode activated, that is sleep demo mode
Regen. Mode Enabled
Self-aging mode enabled
Regen. Mode Active
Self-aging mode activated
Testing Mode Enabled
Testing mode enabled
Testing Mode Active
Testing mode activated
Pwr. Conditioner Mode Enabled
Power conditioner mode enabled
Pwr. Conditioner Mode Active
Power conditioner mode activated
MMS Inv. Manual Off
Power button is pressed on one UPS, and select the parallel system for unified shutdown
MMS Inv. Manual On
Power button is pressed on one UPS, and select the parallel system for unified start-up
Suspend ECO Mode
This alarm appears when input dry contact “Suspend ECO Mode” active. The UPS will stay
in inverter mode and ECO mode will be inhibitted
Inhibit Trans. to Inverter
This alarm appears when input dry contact “Inhibit Trans. to Inverter” active. The UPS will
stay in bypass mode and inverter mode will be inhibitted
Battery Test Stopped
Battery test has been stopped manually
NOTE: 1. For UPS installed with the optional battery monitor, refer to the user manual of the battery
monitor for the alarm messages related to battery cell and charge current.
2. If the alarm is generated as the result of a software value set-up by Vertiv engineer, and you wish to
modify the setting, please get in touch with your local Vertiv customer service center.
Summary of Contents for Liebert EXS 80kVA UPS
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Page 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Page 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Page 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Page 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Page 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...