![Vertiv Liebert EXS 80kVA UPS User Manual Download Page 104](http://html1.mh-extra.com/html/vertiv/liebert-exs-80kva-ups/liebert-exs-80kva-ups_user-manual_1008232104.webp)
96
Vertiv™ Liebert EXS 80kVA UPS User Manual
9 Options
9.7 Output Transformer
This UPS includes an isolation transformer (see
for its position) at the UPS output. This
transformer is installed in the cabinet and provides electrical isolation between the UPS output and the
load.
NOTE: When there is an inner transformer, the C-type breaker of 200A should be installed at upstream
of the UPS.
Figure 9-4 Output transformer and its working principle
Output transformer
Battery
BCB
Maintenance bypass switch Q3
Automatic bypass switch
UPS
Bypass input
Shorting copper bar
of common input
configuration
Mains input
Neutral line
input
Bypass input switch Q2
Rectifier input
switch Q1
Rectifier
DC bus
Inverter
Charger
Automatic
inverter switch
Output
switch Q5
ABC
Output
transformer
abc UPS output
Neutral line
output
N
n
WARNING! 1. The optional output transformer is only suitable for 3-in 3-out mode.
2. When switching on the maintenance bypass switch, the output transformer is still live. During
the transformer maintenance, you must shut down the UPS completely.
Summary of Contents for Liebert EXS 80kVA UPS
Page 1: ...Liebert EXS 80kVA UPS User Manual...
Page 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Page 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Page 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Page 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Page 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Page 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...