REV : 6
REV DATE : 7/17
DPN000275
Page :1 /1
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
PIPING CONNECTIONS
LIEBERT DRYCOOLER
DRYCOOLER MODEL
NUMBER
NUMBER OF COIL
CIRCUITS
INLET & OUTLET PIPE
DIAMETER (INCHES)
-033
4*
1 3/8
-069
4, 8*
1 3/8
-092
6, 12*, 16
1 5/8
-109
8
1 3/8
-109
16*
2 1/8
-112
8
1 3/8
-112
16*, 26
2 1/8
-139
8, 16*
2 1/8
-174
8, 16*, 24
2 1/8
-197
8
1 3/8
-197
16*, 32
2 1/8
-225
16, 26*
2 1/8
-260
16, 24*
2 1/8
-310
16, 32*
2 1/8
-350
16, 32*
2 1/8
-350
48
2 5/8
-352
16, 24*
2 1/8
-419
16, 32*
2 1/8
-466
26
2 1/8
-466
40*
2 5/8
-491
16, 32
2 1/8
-491
48*
2 5/8
DRYCOOLER PIPING CONNECTION SIZES (O.D. Cu)
* = Standard Circuiting
INLET CONNECTION
(UPPER HEADER)
OUTLET CONNECTION
(LOWER HEADER)
Summary of Contents for Liebert Drycooler
Page 1: ...Liebert Air cooled Direct drive Drycooler Installer User Guide 50 Hz and 60 Hz ...
Page 10: ...Vertiv Liebert Drycooler Installer User Guide 6 This page intentionally left blank ...
Page 20: ...Vertiv Liebert Drycooler Installer User Guide 16 This page intentionally left blank ...
Page 24: ...Figure 4 2 Removing Protective Material Vertiv Liebert Drycooler Installer User Guide 20 ...
Page 34: ...Vertiv Liebert Drycooler Installer User Guide 30 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Drycooler Installer User Guide 50 This page intentionally left blank ...
Page 62: ...Vertiv Liebert Drycooler Installer User Guide 58 This page intentionally left blank ...
Page 66: ...Vertiv Liebert Drycooler Installer User Guide 62 This page intentionally left blank ...
Page 68: ...Vertiv Liebert Drycooler Installer User Guide 64 This page intentionally left blank ...
Page 101: ...Vertiv Liebert Drycooler Installer User Guide ...