No. of Fans:
1
2
3
4
Model #:
33, 69, 092, 109, 112
139, 174, 197, 225
260, 310, 350
352, 419, 466, 491
Pump
hp
Ph
F
L
A
W
S
A
O
P
D
F
L
A
W
S
A
O
P
D
F
L
A
W
S
A
O
P
D
F
L
A
W
S
A
O
P
D
208/230/60
0.75
1
12.4
14.3
20
—
—
—
—
—
—
—
—
—
0.75
3
7
7.9
15
10.5
11.4
15
14.0
14.9
20
17.5
18.4
25
1.5
3
10.1
11.8
15
13.6
15.3
20
17.1
18.8
25
20.6
22.3
25
2.0
3
11.0
12.9
20
14.5
16.4
20
18.0
19.9
25
21.5
23.4
30
3.0
3
14.1
16.8
25
17.6
20.3
30
21.1
23.8
30
24.6
27.3
35
5.0
3
20.2
24.4
40
23.7
27.9
40
27.2
31.4
45
30.7
34.9
50
7.5 *
3
27.7
33.8
50
31.2
37.3
60
34.7
40.8
60
38.2
44.3
60
460/60
0.75
3
3.3
3.7
15
5.0
5.4
15
6.7
7.1
15
8.4
8.8
15
1.5
3
4.7
5.5
15
6.4
7.2
15
8.1
8.9
15
9.8
10.6
15
2.0
3
5.1
6.0
15
6.8
7.7
15
8.5
9.4
15
10.2
11.1
15
3.0
3
6.5
7.7
15
8.2
9.4
15
9.9
11.1
15
11.6
12.8
15
5.0
3
9.3
11.2
15
11.0
12.9
20
12.7
14.6
20
14.4
16.3
20
7.5
3
12.7
15.5
25
14.4
17.2
25
16.1
18.9
25
17.8
20.6
30
575/60
0.75
3
2.7
3.1
15
4.1
4.5
15
5.5
5.9
15
6.9
7.3
15
1.5
3
3.8
4.4
15
5.2
5.8
15
6.6
7.2
15
8.0
8.6
15
2.0
3
4.1
4.8
15
5.5
6.2
15
6.9
7.6
15
8.3
9.0
15
3.0
3
5.3
6.3
15
6.7
7.7
15
8.1
9.1
15
9.5
10.5
15
5.0
3
7.5
9.0
15
8.9
10.4
15
10.3
11.8
15
11.7
13.2
15
7.5
3
10.4
12.7
20
11.8
14.1
20
13.2
15.5
20
14.6
16.9
25
Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be adjusted higher than calculations to compensate for
maximum anticipated application temperatures.
* May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before ordering.
Table 6.4 60Hz Electrical Values—Standard Drycoolers with Integral Pump Controls, 1 to 4 Fans
6 Electrical Connections
43
Summary of Contents for Liebert Drycooler
Page 1: ...Liebert Air cooled Direct drive Drycooler Installer User Guide 50 Hz and 60 Hz ...
Page 10: ...Vertiv Liebert Drycooler Installer User Guide 6 This page intentionally left blank ...
Page 20: ...Vertiv Liebert Drycooler Installer User Guide 16 This page intentionally left blank ...
Page 24: ...Figure 4 2 Removing Protective Material Vertiv Liebert Drycooler Installer User Guide 20 ...
Page 34: ...Vertiv Liebert Drycooler Installer User Guide 30 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Drycooler Installer User Guide 50 This page intentionally left blank ...
Page 62: ...Vertiv Liebert Drycooler Installer User Guide 58 This page intentionally left blank ...
Page 66: ...Vertiv Liebert Drycooler Installer User Guide 62 This page intentionally left blank ...
Page 68: ...Vertiv Liebert Drycooler Installer User Guide 64 This page intentionally left blank ...
Page 101: ...Vertiv Liebert Drycooler Installer User Guide ...