8 TROUBLESHOOTING
Symptom
Possible Cause
Check Or Remedy
Unit will not operate
No main power
Check L1, L2 and L3 for rated voltage
Disconnect switch
open
Close disconnect switch
Blown fuse or circuit
breaker tripped
Check fuses or circuit breaker
Control fuse or circuit
breaker tripped
Check for 24VAC. If no voltage, check for short. Replace fuse or
reset circuit breaker.
Improperly wired
Check wiring diagram
No output voltage
from transformer
Check for 24VAC. If no voltage, check primary voltage.
Unit runs, but motor protector
keeps tripping
Motor protector
defective
Replace protector
Motor protector too
small
Check amp. draw
Fan or pump motor
has shorted winding
Repair motor
Low or unbalanced
voltage
Determine reason and correct
Outlet temperature from unit
too high
Low or no coolant flow
See
Pump will not operate or no coolant flow
entry in this table.
Ambient air
temperature higher
than design
Correct possible hot air discharge to fans from another source.
Heat load higher than
design
Check for misapplication, need larger cooler. Correct possible
additional heat load being added to cooling circuit.
Throttling valve
improperly
Reset valve to proper differential pressure.
Liquid squirts from surge tank
fill cap when pump is turned off
Air in system
Vent all high points, repeat as necessary. Check liquid level in
surge tank.
Pump suddenly stops pumping
Clogged strainer or
impeller
Clean out debris.
Pumping suddenly slows
Clogged impeller,
diffuser or line
Clean out debris and use strainer.
Table 8.1 Troubleshooting Symptoms and Checks
8 Troubleshooting
51
Summary of Contents for Liebert Drycooler
Page 1: ...Liebert Air cooled Direct drive Drycooler Installer User Guide 50 Hz and 60 Hz ...
Page 10: ...Vertiv Liebert Drycooler Installer User Guide 6 This page intentionally left blank ...
Page 20: ...Vertiv Liebert Drycooler Installer User Guide 16 This page intentionally left blank ...
Page 24: ...Figure 4 2 Removing Protective Material Vertiv Liebert Drycooler Installer User Guide 20 ...
Page 34: ...Vertiv Liebert Drycooler Installer User Guide 30 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Drycooler Installer User Guide 50 This page intentionally left blank ...
Page 62: ...Vertiv Liebert Drycooler Installer User Guide 58 This page intentionally left blank ...
Page 66: ...Vertiv Liebert Drycooler Installer User Guide 62 This page intentionally left blank ...
Page 68: ...Vertiv Liebert Drycooler Installer User Guide 64 This page intentionally left blank ...
Page 101: ...Vertiv Liebert Drycooler Installer User Guide ...