NOTE: A separate neutral wire does not need to be run to the Liebert® Drycooler.
No. of Fans
Model No.
Voltage
Phase
FLA
WSA
OPD
Standard Models
1
33, 69, 092, 109, 112
208/230
1
4.8
6
15
3
3.5
4.4
15
460
3
1.7
2.1
15
575
3
1.4
1.8
15
2
139, 174, 197, 225
208/230
3
7.0
7.9
15
460
3
3.4
3.8
15
575
3
2.8
3.2
15
3
260, 310, 350
208/230
3
10.5
11.4
15
460
3
5.1
5.5
15
575
3
4.2
4.6
15
4
352, 419, 466, 491
208/230
3
14.0
14.9
20
460
3
6.8
7.2
15
575
3
5.6
6.0
15
6
620, 650, 700
208/230
3
21.0
21.9
25
460
3
10.2
10.6
15
575
3
8.4
8.8
15
8
790, 880, 940
208/230
3
28.0
28.9
35
460
3
13.6
14.0
20
575
3
11.2
11.6
15
Liebert® Quiet-Line Models
1
40, 57, 60
208/230
3
1.8
2.3
15
460
3
0.9
1.1
15
575
3
0.7
0.9
15
2
80, 111, 121
208/230
3
3.6
4.1
15
460
3
1.8
2.0
15
575
3
1.4
1.6
15
3
158, 173, 178
208/230
3
5.4
5.9
15
460
3
2.7
2.9
15
575
3
2.1
2.3
15
4
205, 248
208/230
3
7.2
7.7
15
460
3
3.6
3.8
15
575
3
2.8
3.0
15
Table 6.2 60Hz Electrical Values—Drycoolers without Pump Controls
6 Electrical Connections
41
Summary of Contents for Liebert Drycooler
Page 1: ...Liebert Air cooled Direct drive Drycooler Installer User Guide 50 Hz and 60 Hz ...
Page 10: ...Vertiv Liebert Drycooler Installer User Guide 6 This page intentionally left blank ...
Page 20: ...Vertiv Liebert Drycooler Installer User Guide 16 This page intentionally left blank ...
Page 24: ...Figure 4 2 Removing Protective Material Vertiv Liebert Drycooler Installer User Guide 20 ...
Page 34: ...Vertiv Liebert Drycooler Installer User Guide 30 This page intentionally left blank ...
Page 54: ...Vertiv Liebert Drycooler Installer User Guide 50 This page intentionally left blank ...
Page 62: ...Vertiv Liebert Drycooler Installer User Guide 58 This page intentionally left blank ...
Page 66: ...Vertiv Liebert Drycooler Installer User Guide 62 This page intentionally left blank ...
Page 68: ...Vertiv Liebert Drycooler Installer User Guide 64 This page intentionally left blank ...
Page 101: ...Vertiv Liebert Drycooler Installer User Guide ...