UNIT SIZE, TYPE
10 BAY
16 BAY
12 BAY
16 BAY
10 BAY
16 BAY
NO TRANSFORMER
TRANSFORMER-BASED
NO TRANSFORMER DUAL INVERTER
FRAME RATING,
KVA/KW
15/13.5
20/18
15/13.5
20/18
15/13.5
20/18
Input Data
Nominal Input
Voltage,
VAC
200/208/220/230/240; Single-Phase
200/100, 220/110, 230/115, 240/120, 254/127, 208/120,
173/100, 190/110, 200/115, 220/127; Two-Phase
380/400/415; Three-Phase
—
—
Input Voltage Range
The input voltage range based on the output loading, refer to Table 8.2 on the facing page
Power Factor, Cos
Single-Phase Input, > 0.99;
Three-phase Input, > 0.95
Single-Phase Input, > 0.99
Input Frequency,
Nominal
50/60Hz
Input Current
Distortion, THDi
< 5%
Input Frequency
Range
40 to 70Hz, auto-sensing
Battery Module
Lead-Acid Batteries
Per String
12
Battery Cells Per
String
72
Battery Capacity
36W @ 15min-rate to 1.67V per cell @25
°C (77°F)
Backup Time, Full
Load
5 (for non-redundant system which has equal number of battery strings and power modules)
Maximum Charge
Current
(Full, Load)
Power module internal charger: 1.8A
Charger module: 10A
Nominal Voltage
144 VDC
Recharge Timer
< 5 Hr. to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
Output Data
Output Voltage,
VAC
200/208/220/230/240
Single-Phase
100/100/173/200
110/110/190/220
115/115/199/230
120/120/208/240
Single-Phase
200/100, 220/110, 230/115, 240/120, 254/127, 208/120,
173/100, 190/110, 200/115, 220/127; Two-Phase
Voltage Regulation
±3%
Voltage Stability
(100% Step Load)
±7%
Voltage Recovery
Time
≤ 60 ms
Voltage Distortion
≤ 3%, linear load
≤ 5%, non-linear load
≤ 7%, non-linear load
≤ 5%, non-linear load
Output Frequency
50/60 Hz
Table 8.1 Liebert APS specifications (continued)
Vertiv
| Liebert® APS™ Installer/User Guide |
82
Summary of Contents for Liebert APS series
Page 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Page 6: ...Vertiv Liebert APS Installer User Guide 6...
Page 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Page 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Page 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Page 109: ......