Configuring the Neutral/Earth Jumper
The UPS contains an isolation transformer that generates a neutral conductor for the connected load.
The UPS is a separately-derived source and contains a neutral/earth jumper. You may need to remove a
factory-installed neutral/earth-jumper copper bar to comply with local codes and regulations.
Figure 3.19 Configuring the neutral/earth jumper
Connecting the Cables
NOTE: Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box, see Figure 3.20 below and pull the cables through
them, leaving some slack for installation.
Figure 3.20 Knockouts in units without a transformer
ITEM
DESCRIPTION
ITEM
DESCRIPTION
1
16-bay, with transformer
3
Output-cable knockout
2
12-bay, with transformer
4
Input-cable knockout
Vertiv
| Liebert® APS™ Installer/User Guide |
39
Summary of Contents for Liebert APS series
Page 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Page 6: ...Vertiv Liebert APS Installer User Guide 6...
Page 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Page 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Page 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Page 109: ......