4 COMMUNICATION
The rear panel of the Liebert APS includes the following communication ports:
•
Liebert IntelliSlot™ port—3
•
Dry-contact port—1
•
REPO (Remote Emergency Power Off)—1
•
Long Run Time (LRT) Battery-temperature Probe Terminal—1
•
USB port—1
4.1 Liebert IntelliSlot Ports
The 3 Liebert IntelliSlot communication ports (see Figure 4.1 below) are for communication options,
including the Liebert IntelliSlot Unity card, dry-contact card, Liebert MultiPort and Liebert IntelliSlot EBC
card. The IntelliSlot ports and the USB port may be used at the same time.
Figure 4.1 Liebert IntelliSlot communication port location
ITEM
DESCRIPTION
1
IntelliSlot ports
4.1.1 Liebert IntelliSlot Unity Cards
•
IS-UNITY-LIFE is standard in every Liebert APS. It is used for communication between the
Liebert APS and Vertiv™ Trellis® NMS and LIFE Services.
•
IS-UNITY-DP: is optional in place of the standard card if communication to two third-party
platforms is required. Third-party platforms include SNMP and 485 (Modbus/Bacnet)
protocols. When used, this card also provides communication between the Liebert APS and
Vertiv™ Trellis NMS and LIFE Services. All communication protocols are active simultaneously.
Vertiv
| Liebert® APS™ Installer/User Guide |
51
Summary of Contents for Liebert APS series
Page 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Page 6: ...Vertiv Liebert APS Installer User Guide 6...
Page 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Page 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Page 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Page 109: ......