UNIT SIZE, TYPE
10 BAY
16 BAY
12 BAY
16 BAY
10 BAY
16 BAY
NO TRANSFORMER
TRANSFORMER-BASED
NO TRANSFORMER DUAL INVERTER
FRAME RATING,
KVA/KW
15/13.5
20/18
15/13.5
20/18
15/13.5
20/18
Output Overload
Capability
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec
Table 8.1 Liebert APS specifications (continued)
SYSTEM CONFIGURATION
% UPS LOAD
LOW LIMIT VALUE
HIGH LIMIT VALUE
Dual-Inverter
Configured to 120
or 127 VAC per Phase
>100%
98 ±3.1
139.5 ±3.1
90% ~ 100%
89 ±3.1 ~ 98 ±3.1
70% ~ 90%
74 ±3.1 ~ 89 ±3.1
30% ~ 70%
60.5 ±3.1 ~ 74 ±3.1
<30%
60.5 ±3.1
Dual-Inverter
Configured to 100,
110 or 115 VAC per Phase
>100%
84 ±3.1
90% ~ 100%
80 ±3.1 ~ 84 ±3.1
70%~90%
72 ±3.1 ~ 80 ±3.1
40%~70%
60 ±3.1 ~ 72 ±3.1
<40%
60 ±3.1
Single-Inverter
Transformer-Based and
Transformer-Free
>100%
170 ±5
280 ±5
90% ~ 100%
160 ±5 ~ 170 ±5
70%~90%
140 ±5 ~ 160 ±5
50%~70%
120 ±5 ~ 140 ±5
<50%
120 ±5
Table 8.2 Rated input voltage range (Unit: VAC)
PARAMETERS
AS7EBCNCC1BX000
General and Environmental
Conducted and Radiated EMC Levels
IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety Standards
IEC/EN/AS 62040-1:2008, UL 1778 5
th
Ed and CSA 22.2 No. 107.3
Immunity Standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Table 8.3 Liebert APS external battery cabinet specifications
Vertiv
| Liebert® APS™ Installer/User Guide |
83
Summary of Contents for Liebert APS series
Page 1: ...Liebert APS 5 20 kVA Modular UPS Installer User Guide...
Page 6: ...Vertiv Liebert APS Installer User Guide 6...
Page 10: ...Vertiv Liebert APS Installer User Guide 10 This page intentionally left blank...
Page 50: ...Vertiv Liebert APS Installer User Guide 50 This page intentionally left blank...
Page 76: ...Vertiv Liebert APS Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liebert APS Installer User Guide 80 This page intentionally left blank...
Page 109: ......