Chapter 4 Operator Control And Display Panel 69
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Alarm
Explanation
automatically resets once the overload condition is removed
System Overload
This alarm appears when the total load rises above 105% of the nominal rating of the
parallel system. The alarm automatically resets once the overload condition is removed
Out. Overload
Timeout
The UPS overload status continues and the overload times out.
When the time has expired, the load automatically transfers to the bypass
Load Impact Transfer
A transfer to bypass occurred due to a large step load. The UPS can recover
automatically. Turn on the load equipment in stages to reduce the load impact on the
inverter
Excess Auto Rexfers
The load remains on bypass power owing to excessive number of transfers that occurred
within the one hour
Excess ECO Auto
Xfers
The load remains on bypass power owing to excessive number of transfers that occurred
within the one hour
Load Sharing
Abnormal
The UPSs in a parallel system are not sharing the load current correctly
Other Module Xfer
All UPSs in the parallel system transfer to bypass at the same time when one of them
needs to transfer to bypass. This message appears on the TOUCHSCREEN of the UPS
with passive transfer to bypass
Control Power Fail
The auxiliary power failure or power-off
EPO
EPO button on operator control and display panel pressed or external EPO command
received
Fan Abnormal
At least one fan has fault
Operation Invalid
Maintenance bypass switch is closed when the parallel system is on inverter, or output
switch and maintenance bypass switch are closed when the inverter is on
LBS Active
The LBS setting is active
LBS Abnormal
LBS is abnormal
Input Switch Open
Input switch is open
Maint. Switch Open
Maintenance bypass switch is open
Maint. Switch Closed
Maintenance bypass switch is closed
Bypass Switch Open
Bypass switch is open
Output Switch Open
Output switch is open
Charger Fault
Battery charger has failure
Discharger Curr. Limit Discharge current is over limit, close the discharger
Autostart
After UPS shutdown at EOD, the inverter automatically starts upon mains restoration
Batt. Equalize Charge
The battery is forced to be in boost charge state
Rectifier DSP Update
Rectifier DSP software being updated
Rectifier FPGA
Update
Rectifier FPGA software being updated
Inverter DSP Update
Inverter DSP software being updated
Inverter FPGA Update Inverter FPGA software being updated
Bypass DSP Update
Bypass DSP software being updated
Bypass FPGA Update
Bypass FPGA software being updated
Monitor Update
Monitoring software being updated
Flash Operate Fail
Historical record not saved
Remote Turn On
Turn on the inverter through the service command
Remote Turn On Fail
Caused by invalid operation (maintenance bypass switch closed), DC bus or rectifier not
ready
Remote Turn Off
Turn off the inverter through the service command
No Battery
Check the battery and battery connection
Discharger Fault
Bus voltage abnormal
Battery Reversed
Reconnect battery and check battery wiring
Battery Period
The battery is under automatic periodic battery maintenance test (20% capacity