30 Chapter 3 Electrical Installation
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Pin
Name
Meanings
Pin
Name
Meanings
5
GND_DRY
Dry ground
6
NC
Reserved
7
BCB_ONLine
BCB on line signal
8
NC
Reserved
9
NC
Reserved
10
NC
Reserved
11
GND_DRY
Dry ground
12
NC
Reserved
13
TMP_BAT
External battery
temperature
14
NC
Reserved
15
12V_DRY
Power
16
NC
Reserved
17
GND_DRY
Dry ground
18
NC
Reserved
19
BAT_Ground_FAULT
Battery ground fault
(24V, 10mA)
20
NC
Reserved
3.2.4
Dry Contact Port J26
The dry contact port J26 is shown in Figure 3-9 and described in Table 3-5.
1 3 5 7 9 11 13 15 17 19
J26
21 23 25 27 29 31
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
Figure 3-9 Dry contact port J26
Table 3-5
Description of dry contact port J26
Pin
Name
Meanings
Pin
Name
Meanings
1
Q1 STATUS
Input switch status
(24V/ 10mA rated);
Pin1/Pin3 shorted for Q1
closed
2
GEN MODE
Generator mode
(24V/10mA rated).
Pin2/Pin4 shorted for
generator connected
3
GND_DRY
4
GND_DRY
5
Q2 STATUS
Bypass switch status
(24V/10mA rated);
Pin5/Pin7 shorted for Q2
closed
6
TMP BATT_IN
Reserved
7
GND_DRY
8
+12V_DRY
9
Q3 STATUS
Maintenance switch
status (24V/10mA
rated); Pin9/Pin11 open
for Q3 closed
10
Reserved
11
GND_DRY
12
GND_DRY
13
Q5 STATUS
Output switch status
(24V/10mA rated); Pin13
/Pin15 shorted for Q5
closed
14
ENV_DET
Battery room
temperature status
(24V/10mA rated).
Pin14/Pin16 shorted for
battery room
temperature abnormal
15
GND_DRY
16
GND_DRY