Chapter 8 Options 125
Liebert EXM 80kVA ~ 200kVA UPS User Manual
8.2.8
SIC Card
The SIC card is a network management card. It can make the UPS developed by Vertiv Tech Co., Ltd have
network communication capability. It can also be connected to the IRM series sensor to provide
environment monitoring function. When the intelligent equipment generates an alarm, the SIC card can
notify the user by recording the log, sending trap information, and sending a mail. The SIC card supports
Modbus RTU protocol.
Preparation
1. Prepare the installation tools, including a cross head screwdriver.
2. Check that all installation materials are present and complete, including an SIC card.
Procedures
Note
There is no need to shut down the UPS during SIC card installation, because the SIC card is hot pluggable.
Warning
Some electron components in SIC card are sensitive to static, therefore, do not touch the electron components or
circuit in SIC card by hand or other conductive materials, so as to protect the SIC card against static shock. When
removing or installing the SIC card, hold the card side edge to operate it.
The SIC card should be installed in the Intellislot port (see Figure 3-6) in the UPS. See Table 3-8 for
installation positions of optional cards.
Method for installation:
1. Remove the cover of Intellislot port. Note to reserve the removed screws and take care of the cover for
future use.
2. Insert the SIC card (along two sides of the Intellislot port) into the port position recommended in
Table 3-8, and then fasten the screws.
For more information of the SIC card, refer to
Site Interface Web/SNMP Agent Card User Manual
in
accessory.
Refer to
3.2.10 Signal Cable Connection Steps
for the cabling and routing of the signal cables.
8.2.9
IS-Relay Card
The appearance of the IS-Relay card is shown in Figure 8-17.