Chapter 3 Electrical Installation 31
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Pin
Name
Meanings
Pin
Name
Meanings
17
GND_DRY
External maintenance
isolation switch status
(24V/10mA rated); Pin17
/Pin19 open for QOP
closed
18
CHG SHUT
Charger shutdown
(24V/10mA rated).
Pin18/Pin20 shorted
for charger off
command
19
QOP STATUS
20
GND_DRY
21
QBP STATUS
External maintenance
switch status
(24V/10mA rated);
Pin21/Pin23 shorted for
QBP closed
22
QE STATUS
External output switch
status (24V/10mA
rated); Pin22/Pin24
open for QE closed
23
GND_DRY
24
GND_DRY
25
NC
Reserved
26
NC
Reserved
27
UT1 485+
RS485 channel #1, 485+
28
UT2 485+
RS485 channel
#2,485+
29
UT1 485-
RS485 channel #1, 485-
30
UT2 485-
RS485 channel #2,
485-
31
GND_MON
Reserved
32
NC
Reserved
Note
For dry contact port J26, Pin28, Pin30 and Pin27, Pin29 must adopt the metal wire shielded twisted-pair cable, and
the end connecting to the UPS must be well connected to the enclosure.
3.2.5
Programmable Dry Contact Ports J23 ~ J25
The dry contact ports J23 ~ J25 are shown in Figure 3-10 and described in Table 3-6 and Table 3-7. The
dry contact voltages are 24Vdc/250Vac, and the current is 5A. 1, 3, 5 is a group of dry contacts, and 2, 4, 6
are another group of dry contatcs. These six-goup of dry contacts are programmable via the Paramset,
and you can select any one from the output signals 1~9 in Table 3-6.
1
3
5
J23
1
3
5
1
3
5
J24
J25
2
4
6
2
4
6
2
4
6
Figure 3-10 Dry contact ports J23 ~ J25
Table 3-6
Selectable dry contact ports
Port
Pin
Meanings
1. Bypass
back-feed
Normally open
contact
Bypass back-feed normally open contact. Closed when there is
bypass back-feed
Common contact
Bypass back-feed common contact
Normally
closed
contact
Bypass back-feed normally closed contact. Open when there is
bypass back-feed
2. Inverter state
Normally open
contact
Inverter state normally open contact. Closed when the inverter is on
Common contact
Inverter state common contact
Summary of Contents for EXM 0080kTK16FN01000
Page 2: ......
Page 14: ......
Page 132: ...118 Chapter 8 Options Liebert EXM 80kVA 200kVA UPS User Manual...