4.2.4 Dry Contact Port J8
The dry contact port J8 is shown in Figure 4.7 below and described in Table 4.7 below. The dry contact voltages are 24
Vdc/250 Vac, and the current is 5 A.
F igu re 4.7 Dry co n tact po rt J 8
Port
Pin
D efault s ig nal
1. Bypass Backfeed
J8-1
Normally open. Closed when bypass has backfeed
J8-3
Bypass backfeed protection relay common
J8-5
Normally closed. Open when bypass has backfeed
2. Input Backfeed
J8-2
Normally open. Closed when rectifier has backfeed
J8-4
Rectifier backfeed protection relay common
J8-6
Normally closed. Open when rectifier has backfeed
T able 4.7 Descriptio n o f dry co n tact po rt J 8
4 Electrical Installation
47
Vertiv™ Liebert® APM Plus User Manual