![Vertiv APM 0250kMK16FN02000 User Manual Download Page 26](http://html1.mh-extra.com/html/vertiv/apm-0250kmk16fn02000/apm-0250kmk16fn02000_user-manual_1008197026.webp)
ECO mode
If ECO mode is selected, all power switches and the battery switches are closed except for the maintenance bypass switch,
and the system prefers to put the load on the bypass, to achieve the aim of energy-saving. When the bypass supply is within
the range of normal frequency and normal voltage (adjustable), the load is powered by the bypass, with the inverter on
stand-by; when the voltage and/or frequency of the bypass supply are beyond the pre-defined and adjustable limits, the
system will transfer to the inverter output, and the transfer time for switching from bypass to inverter is less than 2 ms
(uninterrupted) and less than 5 ms (interrupted). In this mode, the system can normally charge the battery.
F igu re 2.7 Sch em atic diagram o f ECO m o de
N o.
D es crip tion
1
Bypass input
2
Bypass input switch
3
Static switch
4
Mains input
5
Rectifier input switch
6
Rectifier
7
Inverter
8
Automatic Inverter switch
9
Output switch
10
UPS output
11
Battery
12
Battery charger
If ECO mode is required, adjust corresponding parameters through the touch screen.
The operation method of ECO mode is the same as described in Chapter 5 UPS Operation Introduction. However, in normal
mode, the load is powered by the bypass, the inverter indicator is flashing, and the touch screen displays 'Bypass mode'.
W A R N IN G ! In ECO m o de, th e lo ad is n o t pro tected again st m ain s disto rtio n .
Frequency converter mode
2 Overview
18
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...