A larm
E xp lanation
Bypass overcurrent
The bypass current is outside the rated current
Bypass backfeed
The bypass backfeed is faulty
Bypass Overtemperature
The bypass has overtemperature
Bypass in Charge
The bypass detects an inverter signal when the system runs normally. When the output voltage is abnormal, the system will
transfer to bypass mode for power supply
Bypass Neutral Lost
The bypass lacks N
Bypass in Setting
The bypass module is initialized and synchronized
Rectifier Fault
Bus voltage abnormal or battery SCR short circuit
DC Bus Overvoltage
The rectifier, inverter and battery converter shut down because the DC bus voltage is too high. The load transfers to bypass
DC Bus Abnor. Shutdown
The DC bus voltage is abnormal and results in inverter shutdown. The load transfers to bypass
Inverter Asynchronous
The output voltage and bypass voltage are misaligned in phase. This alarm resets automatically once the condition is no
longer true
Inverter Fault
Inverter output voltage outside specifications. Load transfers to bypass
Inverter Relay Fail
At least one of the inverter relays is opened or shorted. This fault is locked until mains power-off
Output Fuse Fail
At least one of the inverter output fuses is blown
Output Volt. Abnormal
At least one phase of the output voltages is abnormal
Output Overload
This alarm appears when the load arises above 105% of the nominal rating. The alarm automatically resets once the
overload condition is removed
System Overload
This alarm appears when the total load rises above 105% of the nominal rating of the parallel system. The alarm
automatically resets once the overload condition is removed
Out. Overload Timeout
The UPS overload status continues and the overload times out. When the time has expired, the load automatically transfers
to the bypass
Load Impact Transfer
A transfer to bypass occurred due to a large step load. The UPS can recover automatically. Turn on the load equipment in
stages to reduce the load impact on the inverter
Excess Auto Rexfers
The load remains on bypass power owing to excessive number of transfers that occurred within the one hour
Excess ECO Auto Xfers
The load remains on bypass power owing to excessive number of transfers that occurred within the one hour
Load Sharing Abnormal
The UPSs in a parallel system are not sharing the load current correctly
Other Module Xfer
All UPSs in the parallel system transfer to bypass at the same time when one of them needs to transfer to bypass. This
message appears on the TOUCHSCREEN of the UPS with passive transfer to bypass
Control Power Fail
The auxiliary power failure or power-off
EPO
EPO button on operator control and display panel pressed or external EPO command received
Fan Abnormal
At least one fan has fault
Operation Invalid
Maintenance bypass switch is closed when the parallel system is on inverter, or output switch and maintenance bypass
switch are closed when the inverter is on
LBS Active
The LBS setting is active
LBS Abnormal
LBS is abnormal
Input Switch Open
Input switch is open
T able 5.4 A larm list (co n tin u ed)
5 Operator Control and Display Panel
98
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...