3.7 Mechanical Requirement
3.7.1 Composition
As a cabinet of 600 mm width, the system provides the options such as rectifier input switch, bypass input switch, and
output switch.
3.7.2 Moving Cabinet
W A R N IN G !
1. T h e liftin g equ ipm en t fo r m o vin g th e UP S cabin et m u st h ave en o u gh lift capacity.
2. T h e cen ter o f gravity o f th e UP S cabin et is h igh ; avo id fallin g o ver du rin g th e cabin et
m o vem en t.
3. Vertical h an gin g o f cabin et is n o t allo wed.
Ensure that the weight of the UPS does not exceed the capacity of the lifting equipment. For the UPS weight, refer to Table
12.3 on page 176.
The UPS cabinet can be moved by forklift or other similar lifting equipment.
For short distance movement, the castors can be used.
3.7.3 Clearance
Because the UPS has no perforated doors at the two sides, there is no special clearance requirement on the two sides.
Besides the local regulations, to enable routine tightening of the power terminals within the UPS, it is recommended that
clearance around the front of the UPS should be larger than 1200 mm and sufficient to enable free passage of personnel with
the door fully open. If top fan (option) is configured, maintain at the top of the cabinet a clearance at least 500 mm to permit
adequate circulation of air coming out of the UPS.
3.7.4 Cable Access Mode
For further description, refer to Power Cable Connection Steps and Signal Cable Connection Steps
3 Mechanical Installation
31
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...