28 Chapter 4 Use Of The Controller
NetSure 731 CC2, NetSure 731 C62 Series Power Supply System User Manual
The Figure 4-16 screen includes alarm serial No./ alarm total number, alarm name, alarm level and alarm time. The
alarm generating time determines the sequence it is displayed, with the latest alarm displayed first. Use
▲ or ▼ to
view all active alarms.
When querying the
rectifier alarms, press ► to display the rectifier ID, and the green indicator of the rectifier will blink.
In case of battery test alarm or maintenance time alarm, press
► to display the prompt information screen, then
press the ENT key to confirm that the alarm is cleared. The active alarms in the controller are given in Table 4-4.
Table 4-4 Active alarm of the controller
No.
Alarm type
Alarm
Description
1
Rectifier alarm
Rect AC Fail
Press
► to brow se the serial No. of the faulty rectifier
2
Rect Over Temp
3
Rect Fault
4
Rectifier alarm
Rect Protect
Press
► to brow se the serial No. of the faulty rectifier
5
Rect Fan Fails
6
Rect Derated
7
Rect Not Respond
8
Multi-Rect Alarm
9
Rectifier Lost
You can clear this alarm manually
1
AC alarm
SPD Fault
SPD fault is the alarm of Digital 1
2
Digital Alarm
3
AC High
4
AC Low
5
AC PH Fail
6
Mains Failure
1
DC alarm
DC Volt High+
2
DC Volt Low
3
DC Volt Low -
4
Batt Over Temp
5
Batt Temp High Alarm
6
Batt Temp Low Alarm
7
Ambient Temp High Alarm
8
Ambient Temp Low Alarm
9
T No Probe
10
Sensor Fault
11
LVD
12
BLVD
13
Load Fuse Alarm 1
14
Load Fuse Alarm 2
15
Load Fuse Alarm 3
16
Load Fuse Alarm 4
17
Load Fuse Alarm 5
18
Load Fuse Alarm 6
19
Aux Load Fails
20
Batt Fuse Alarm 1
21
Batt Fuse Alarm 2
22
Batt 1 Curr High
1
Battery
management alarm
Non Float Status
2
Batt Discharge
3
Load Share Alarm
4
Batt Test Fail
Press
► to prompt you to clear this alarm
5
Short Test Fail
6
Save Pow er
7
Save Pow er Fault
1
Controller
self-detect alarm
SelfDetect Fail
2
Manual Mode
3
Volt Discrepancy
4
Maintain Alarm
5
Alarm Block