14
20307393
5" x 8" DVP Termination Kit
Install Vertical Termination Cap
To attach the vertical termination cap, slide the inner col-
lar of the cap into the inner flue of the vent section and
place the outer collar of the cap over the outer flue of the
vent section.
Secure the cap by driving the three self-tapping screws
(supplied) through the pilot holes or dimples in the outer
collar of the cap into the outer flue of the vent. See Figure
26.
Termination Cap
(1 of 3)
Storm
Collar
Screws
Caulk
Figure 26 Secure with Screws
Attaching Flexible Venting to Vertical
Termination Kit
1. Attach the inner flex adapter to the inner pipe of the rig
-
id pipe length using three (3) self tapping #10 screws.
2. Attach the outer flex adapter to the outer pipe of the
rigid pipe lenth using three (3) self tapping #10 screws.
3. Attach the 5" and 8" flex pipe to the flex pipe adapter in
the same manner as the starting adapter. See Figure
28.