WDV Series Gas Fireplace
SIGNATURE COMMAND SYSTEM OPERATION
Set temperature and the Room temperature. There is no
manual flame height adjustment. The fan speed will also
automatically adjust if turned on.
NOTE:
there will a 10 second delay for the flame
adjustment when the fireplace is turned on.
1. When Set Temp. is 3° F or higher than Room Temp.,
flame height will be on High.
2. When Set Temp. is 2° F higher than Room Temp.,
flame height will be on Medium.
3. When Set Temp. is 1° F higher than Room Temp.,
flame height will be on Low.
4. When Set Temp. is equal to Room Temp., flame height
does not change (stays on low).
5. When Set Temp. is lower than Room Temp., the
fireplace will be shut off.
6. When Set Temp. is 1° F higher than Room Temp.,
again the flame height will be on Low.
7. the fan speed follows the flame height, if the fan is
turned on.
To exit Smart Mode
®
thermostat and shut off the fireplace;
a.
push and hold the THERMO buttons for 3
seconds, Or
b. press the OFF button, Or
c. slide down on the arrow buttons.
To shut off the Smart Mode
®
thermostat option and return
to regular thermostat mode, press and hold the THERMO
button and the ON/UP button at the same time for 3
seconds again.
BLOWER SPEED CONTROL
Figure 52
NOTE:
Blower will only work with
flame on.
The blower speed control function
is used to adjust the speed of the
blower connected to the Signature
Command System. There are four
speed levels, Off, Low, Medium,
High.
1. Press the FAN button to enter
the blower speed control mode.
The fan icon will start flashing.
2. Press the ON/up and OFF/
down button to increase/
decrease the blower speed.
3. Press the fan button again to confirm the speed
setting. If the fireplace is on, the blower speed will take
effect right away; if the fireplace is off, the receiver will
remember this setting and the blower is still off (see
blower On Delay and Off Delay in the next section).
4. After the signal is sent, the ON/up and OFF/down
buttons become flame height controller again.
5. When the fan button is flashing, slide up and down on
the arrow buttons will turn the blower speed to High
or Off directly without pressing the fan button again to
confirm.
6. If the blower is turned on using the FAN button, the
blower speed will adjust automatically when using
Smart Mode
®
thermostat (See Smart Mode
®
thermostat
section).
BLOWER ON DELAY TIME AND OFF DELAY
TIME SETUP
Figure 53
1. Hold the FAN button for 3
seconds until two numbers
appear on the LCD screen.
The left number is blower On
Delay and the right number is
blower Off Delay Time.
2. When the first number is
flashing, use the ON/up button
to set the desired On Delay
Time from 0 to 15 min.
3. Press the OFF/down button
to jump to the Off Delay Time
setup.
4. When the second number is
flashing, use the ON/up button
again to set the desired Off Delay Time from 0 to 15
min.
5. Press the OFF/down button again to finish the setup
and the new settings will be transmitted to the receiver.
6. The default settings are 5 minutes for the On Delay
Time and 8 minutes for the Off Delay Time, as shown.
LIGHT BRIGHTNESS CONTROL
Figure 54
The light brightness control
function is used to adjust the
brightness of the light bulbs
connected to the AC module
on the Signature Command
System. There are four light
brightness levels defined: Off,
Low, Medium, High
1. Press the LIGHT button to
enter the light brightness
control mode. The LIGHT
icon will start flashing.
2. Press the On/up and OFF/
down buttons to increase/
decrease the light brightness
(Off-Low-Medium-High).
3. Press the light button again to confirm the setting. The
new setting will be transmitted to the receiver.
4. After the signal is sent, the On/up and Off/down buttons
become flame height controller again.
5. When the light button is flashing, slide up and down on
the arrow buttons will turn the light brightness to HIGH
or Off directly without pressing the light button again to
confirm
FP2657
Light bright control
Figure 54
FP2656
blower delay setup
Figure 53
FP2655
blower speed control
Figure 52