20306744
17
WDV Series Gas Fireplace
VENTING INSTALLATION
VERTICAL (THROUGH-THE-ROOF)
APPLICATIONS
This gas fireplace has been approved for,
•
Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 20
NOTE:
Horizontal and vertical sections of this vent system
require a minimum 1" clearance to combustibles at the top,
sides and bottom.
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation
= 270°
12" Min.
1
2
3
4
1
2
3
4
FP1179
max bends
Figure 21 -
Maximum Elbow Usage
FP1179
•
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450 mm).
Example:
Maximum horizontal length
No elbows = 10’ (3 m)
1x45° elbows = 8.5’ (2.6 m)
2x45° elbows = 7’ (2.1 m)
•
A minimum of an 12' (3.6 m) vertical rise is required.
•
Two sets of 45° elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m)
of vent pipe can be used between elbows.
Figure 21
•
The maximum angular variation allowed in the system
is 270°.
Figure 21
FP1183
max height
40' Maximum Height
12' Minimum Height
10'
Maximum
Support Straps
Every 3'
12" Min.
FP1183
Figure 20 -
Support Straps for Horizontal Runs
For models purchased after 4/16/15, please see addendum.