3
20307393
5" x 8" DVP Termination Kit
ASSEMBLE DVP VENT SECTIONS
Attach the First Vent Component to Starter Collar
To attach the first vent component to the starting collar of
the appliance:
• Slide the male end of the inner flue over the inner collar
of the appliance, at the same time, slide the outer flue
over the outer collar of the appliance.
• Push the pipe section into the appliance collar until all
the lances have snapped in place.
• Tug slightly on the section to confirm it has completely
locked into place.
Note: The end of the pipe sections with the lances/
tabs on it will face toward the appliance.
Commercial or High-Rise Applications
For installation into a commercial or high-rise application:
All outer pipe joints must be sealed with high temperature
aluminum foil tape, including the slip section that connects
directly to the horizontal termination cap.
•
Only outer pipes are to be sealed. Do not seal the
inner flue. All unit collar, pipe, slip section, elbow and
cap outer flues shall be sealed in this manner, unless
otherwise stated.
Once both inner and outer flues are started, press section
A onto section B firmly until all lances have snapped
into place. Check to make sure they have snapped
together (see Figure 3) and the seams are not aligned
(see Figure 4). Tug slightly on section A to confirm it has
completely locked into place.
It is acceptable to use screws no longer than 1 in. to hold
outer pipes together. If predrilling screw holes do NOT
penetrate inner pipe.
For 90° and 45° elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer flue at the horizontal elbow joint to prevent
the elbow from rotating. Use screws no longer than 1 in. If
predrilling screw holes do NOT penetrate inner pipe.
Assemble Pipe Sections
Insert the inner flue of section A into the flared inner flue
of section B. (See figure 2).
Start the outer flue of section A over the outer flue of
section B.
A
B
Figure 2 Inner/Outer
WARNING
Risk of Fire/Explosion/Asphyxiation! Improper support
may allow vent to sag and separate. Use vent run
supports and connect vent sections per installation
instructions.
DO NOT
allow vent to sag below connection
point to appliance.
A
B
Figure 3 Snapped
ATTENTION
For use on VCG fireplaces certified to ANSI Z21.50/CSA
2.22 and ANSI Z21.88/CSA 2.33 standards.
ATTENTION
The vent kits described in this manual are tested as part
of a system certified to CSA/ANSI standards to work
with DVP vent lengths certified by UL/ULC and SLP
termination vent kits approved by CSA.