Oxford Direct Vent / Natural Vent Gas Heater
30005123
Thermostat connection (optional)
Use only a thermostat rated for 500 millivolts.
Check the table below for the appropriate gauge thermo-
stat wire to use for the length of lead required in your in-
stallation.
Thermostat
Wire / Gauge
Maximum Run
18
20 feet
16
20 - 40 feet
14
up to 60 feet
1. Install the wall thermostat in the desired location and
run the wires to the stove location. Terminate these
leads with 1/4” female connectors.
2. Connect the thermostat wires to the valve. (Fig. 42)
Install the Stove Front
Insert the handle stub into the hole in the front casting.
Fasten in place witht he 3/8” locking nut provided. (Fig.
43)
The front attaches to the stove by four steel tabs that en-
gage with corresponding cast ribs onto the sides and bot-
tom of the stove body. Position the front about 3” down
from stove top and lift the plate to engage the upper tabs
behind the adjacent ribs on the sides. (Fig. 44) Then lower
the front into position, so the lower tabs engage with the
corresponding ribs at the bottom.
When properly installed, the bottom of the stove front can-
not be pulled away from the sides without also lifting it.
ST773
handle assy
6/6/03
3/8” Locking
Nut
Handle Stub
ST773
Fig. 43
Insert handle stub into hole in front. Secure with 3/8”
locking nut.
ST1126
install stove front
Engage steel tabs behind
the cast iron bosses
Bottom tabs engage
notch in the leg
ST1126
Fig. 44
Install the front plate.