background image

22

Oxford Direct Vent / Natural Vent Gas Heater

30005123

8.  The air shutter is located on the bottom of the burner 

to the left. (Fig. 37) Unfasten the two nuts holding the 

shutter in place. The shutter may be adjusted between 

the factory adjusted 1/2” to fully open. Reassemble the 

shutter to allow the rear injector air inlet to close from 

the minimum 1/2” opening to fully open. (Fig. 39) You 

may have to try more than once to find the correct air 

shutter opening for best results depending on your al-

titude.

ST352

jefferson

air shutter

new position

3/20/00   djt

Air Shutter

(Original Position)

Burner

See Table 1

ST352

Fig. 38

  Air shutter in original from-the-factory position.

Should color need further adjustment, repeat steps 1 

- 12 for air shutter adjustment.

ST351

jefferson

air shutter

original position

3/20/00   djt

Front Injector 

Air Inlet

Air Shutter

(May be adjusted up to fully open)

Burner

ST351

Rear Injector Air Inlet

Fig. 39

  Air shutter adjusted.

9.  Refasten the two nuts and assemble the burner  into 

the unit by sliding the burner in at an angle with the 

left side  lower  than the right  side. Slide  the left side 

onto the injectors. Lower the right hand side down into 

place. Make sure the burner is as far left as possible 

and the injector shoulders are inside the burner. 

NOTE:

 

It is very critical to keep the left burner leg, which holds 

the injectors, at a 90° angle to the base. (Fig. 40) This 

keeps the orifices aligned with tubes on the inside of 

the burner. Failure to do so could affect the flame ap-

pearance and performance of the unit.

10.Refasten the right and left log bracket assembly.
11.Refasten the rear log bracket.
12.Replace logs.
13.Replace glass and stove front.
Follow lighting instructions on Page 25. Check flame color 

appearance. 

NOTE:

 Allow stove to burn for at least 1/2 

hour to establish full flame color.

ST353

air shutter adjust

burner replace

3/20/00    djt

90°

Left Burner Leg

Injector Shoulder

ST353

Fig. 40

  Be sure to maintain 90° angle at left burner leg.

complete the Assembly

•  Open the swiveling latches (cams) on the top left and 

right corners of the glass frame.

•  Position  the  glass  and  frame  against  the  firebox  by 

placing the bottom edge on the brackets on the bottom 

face of the firebox.

•  Swing the assembly against the firebox, and close the 

latches firmly against the pins protruding from the fire-

box top.

Install ON/OFF Switch

The switch assembly parts are found in the parts bag.
1.  Attach switch assembly to left rear side of stove shroud 

(when  facing  shroud)  using  two  screws  and  existing 

holes in shroud. (Fig. 41)

2.  Run wires down back of stove, under bottom of rear 

shroud to valve.

3.  Attach wires to valve terminals. (Fig. 42)

ST315

attach switch assy

1/31/00   djt

Existing Holes

Switch Assembly

Screws

ST315

Fig. 41

  Attach switch assembly to rear shroud.

PILO

T

ADJ

TP

TH

TPTH

ST228

attach switch

wires to valve

12/99

ST228

Fig. 42

  Attach switch wires to valve.

Summary of Contents for OXDV30NV

Page 1: ...LEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE INSTALLER CONSUMER SAFETY INFORMATION FOR YOUR SAFETY Installation and service must be performed by a qualified installer service agency or the gas supplier This appliance may be installed in an after marketpermanentlylocatedmanufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas i...

Page 2: ...irements and Options Direct Vent ONLY 13 Install the Optional Fan 14 Venting System Assembly Direct Vent 15 Install Vent Adapter Pipe Vermont Castings Group Vent Components 15 Install Vent Adapter Pipe Dura Vent Components 16 Side Wall Termination Assembly 15 Vent Termination Below Grade 18 Vertical Through the Roof Vent Assembly 18 Venting System Assembly Natural Vent 19 Install the Vent Pipe 19 ...

Page 3: ...om the room for combustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installed in an aftermarket manufac tured mobile home where not prohibited by state or local codes WARNING Operation of this heater when not connected to a properly installed and maintained venting system can ...

Page 4: ...haust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no lessthanone half 1 2 inchinsize GASVENTDIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installationunless uponinspection theinspectorobserves carbon mo...

Page 5: ...ve is shipped from the factory as a Direct Vent Gas Heater This heater may be converted into a Natural Vent unit in the field If a Natural Vent heater is desired the FSDHAG Draft Hood must be directly installed to the top of the unit according to the installation instructions The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item When the stove is converted to Natural ...

Page 6: ... Requirements Minimum Clearances to Combustible Materials Measure side clearances as shown in Figures 5 and 6 from the outer edge of the cast iron stove top Measure rear clearances from the outermost surface of the steel rear skirt The heater is approved for installation into an alcove con structed of combustible materials to the dimensions and clearances shown on the next page The same clearances...

Page 7: ... clearances to ceiling or alcove Wall Centerline from Floor ST1121 wall thimble A A Effective Minimum Wall Thimble 57Z x 1461 mm Vermont Castings Group Pipe Centerline 53Z x 1359 mm Simpson DuraVent Pipe ST1121 Fig 5 Minimum wall thimble centerline Hearth Requirements The heater must be installed on rigid flooring When the heater is installed directly on any combustible surface other than wood flo...

Page 8: ... and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370 m WARNING Improper installation adjustment alter ation service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assis tance or additional information consult a qualified installer service agency or the gas supplier Horiz...

Page 9: ...lanning the installation consider the location of the vent terminal and clearances Some of the most com mon clearances to keep in mind are shown in Figure 10 Important All vent clearances must be maintained Check your vent termination clearances against Fig ures 9 through 11 The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is opera...

Page 10: ...nals shall not be recessed into a wall or siding Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes gar den sheds fences decks or utility buildings within 24 from the front of the termination hood Do not locate termination hood where excessive snow or ice build up may occur Be sure to check vent termina tio...

Page 11: ...or assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other appliances appliances 10 000 Btuh 3kW and 23cm for appliances 10 000 100 000 Btuh 30kW 36 91cm Btuh 3kW and 50 000 Btuh for appliances 100 000 B...

Page 12: ...or plate supplied with the stove is not used Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 152 mm Noncombustible 2 51 mm F Combustible 6 152 mm Noncombustible 2 51 mm G Balcony with no side wall M Combustible Noncombustible 12 305 mm M Balcony with perpendicular side wall M 12 305 mm P 6 152 mm...

Page 13: ...n Through the Wall Vent Kit 7TFSSK 1 90 Degree Elbow CG 1 24 termination pipe CG 1 24 44 Adjustable Section 1 Side Wall Termination cool touch with siding shield 1 Firestop 1 Zero clearance sleeve 1 Hardware package 1 Finishing plate CG 1 Finishing collar CG 4 Charcoal Gray flue pipe rings Vertical Termination Kit 1 12 6 12 Pitch 7TDVSKVA 1 Combination Horizontal Offset Roof Support 1 Vertical Ter...

Page 14: ...ponents 2 Remove the rear skirt insert panel at the bottom of the Rear Skirt Fig 13 and fasten the blower assembly to the firebox back with the two Phillips pan head bolts originally installed in the firebox back 1 Fig 14 3 Attach the snapstat assembly to the snapstat bracket with two sheet metal screws 2 Fig 14 Attach the snapstat bracket to the stove with a hex head bolt passing through the brac...

Page 15: ...chwest restictor plate 5 15 03 ST759 Fig 16 Install the restrictor plate only if required for the vent ing configuration Refer to Page 9 2 Attach Inner Starter Pipe found in with the logset to the next section of inner pipe Run a bead of sealant about 1 2 from the upper end of the Inner starter pipe and join the two sections together Drill three pilot holes into the Inner Starter and se cure the a...

Page 16: ...er pipe ST763 DW dura vent attach outer assy ST763 Fig 21 Simpson DuraVent install outer adapter pipe Side Wall Termination Assembly 1 Locate the vent opening on the wall Refer to Figure 5 Page 7 to determine the opening centerline It may be necessary to first position the stove and measure to find the hole location Depending on whether the wall is made of combustible materials cut the opening to ...

Page 17: ...f installing a second 90 elbow Fig 25 8 Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve Seal the joint inside the wall plate if needed to keep cold air from being drawn into the home 9 Seal the ends and connect the horizontal pipe to the elbow Fasten the wall plate to the pipe with three sheet metal screws Slide the trim collar up a...

Page 18: ...chors Waterproof Seal Around Pipe ST219 Fig 29 Use extension brackets to mount snorkel against recessed wall If the foundation is recessed use extension brackets not supplied to fasten the lower portion of the snorkel Fas ten the brackets to the wall first and then fasten to the snorkel with self tapping 8 x 1 2 sheet metal screws Extend the vent pipes out as far as the protruding wall face Fig 29...

Page 19: ...es of B vent pipe use components from one maker or the other Follow the vent component maker s instructions exactly The heater will also accept standard or enamelled 7 150 mm diameter pipe around the Type B venting for deco rative purposes only Fig 32 NOTE The restrictor plate supplied with the stove is not used for Natural Vent applications ST358 DW Decorative pipe around b vent 5 15 03 djt Decor...

Page 20: ...side of the firebox 5 Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs Use the lava rock to cover brackets on the burner Fig 35 LG141 Stardance Install logs 1 12 11 00 djt Left Log Right Log Rear Log Decorative Grate LG141 Fig 34 Install the back left and right logs Connect the Gas Supply Line Check the Rating Pl...

Page 21: ...with 3 8 NPT nipple on the valve side and 1 2 propane gas supply line with an input of 28 000 BTUs at a manifold pressure of 10 0 and minimum inlet supply for adjustment of 11 0 w c Air Shutter Adjustment The Oxford is shipped from the factory with the air shut ter adjusted to the minimum allowed opening Refer to Table 1 Based on the altitude where the stove is located a shutter adjustment is acce...

Page 22: ...lds the injectors at a 90 angle to the base Fig 40 This keeps the orifices aligned with tubes on the inside of the burner Failure to do so could affect the flame ap pearance and performance of the unit 10 Refasten the right and left log bracket assembly 11 Refasten the rear log bracket 12 Replace logs 13 Replace glass and stove front Follow lighting instructions on Page 25 Check flame color appear...

Page 23: ...in place witht he 3 8 locking nut provided Fig 43 The front attaches to the stove by four steel tabs that en gage with corresponding cast ribs onto the sides and bot tom of the stove body Position the front about 3 down from stove top and lift the plate to engage the upper tabs behind the adjacent ribs on the sides Fig 44 Then lower the front into position so the lower tabs engage with the corresp...

Page 24: ...assistance Do not operate the heater until the pilot flame is correct Follow regular maintenance procedures as described on Page 30 ST769 Dutchwest pilot location 5 15 03 djt Pilot Assembly ST769 Fig 45 Pilot assembly location Flame Temperature Adjustment For stoves equipped with HI LO valves flame adjustment is accomplished by rotating the HI LO adjustment knob located near the center of the gas ...

Page 25: ...uctions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone To Turn Off Gas To Heater Lighti...

Page 26: ...t burner assembly utilizes both a thermocouple and a thermopile The thermocouple operates the main valve operation On and Off Clean and or adjust pilot for maximum flame impingement on thermopile and thermocouple Turn valve knob to Pilot Maintain flow to pilot millivolt meter should read greater than 10mV If the reading is okay and the pilot does not stay on replace the gas valve NOTE An interrupt...

Page 27: ...t the top left and right corners of the glass frame Fig 59 Page 31 3 Pull the top edge of the glass and frame assembly away from the firebox face Place the assembly out of the way on a flat padded surface such as a counter protected by a towel 4 Remove the logset from the firebox 5 Remove the rear log bracket by unfastening the screw Fig 49 6 Remove the right and left log bracket assembly by unfas...

Page 28: ...106b Fig 55 Remove pilot orifice Pilot type 2 Loosen pilot hood turning counterclockwise using a 7 16 wrench Fig 54 NOTE You may use pene trating oil to prevent pilot hood threads from seizing up Remove pilot orifice with needlenose pliers Fig 55 NOTE Use a wrench to hold pilot tube in place while removing the orifice Install the conversion orifice Reinstall pilot hood and tighten until mark on pi...

Page 29: ...er adjust burner replace 3 20 00 djt 90 Left Burner Leg Injector Shoulder ST353 Fig 56 Be sure to maintain 90 angle at left burner leg Conversion to Natural Gas Input BTU h Kit Front Part Rear Part Minimum Maximum 30005155 54 055 30000514 44 086 30000334 19 000 28 000 Conversion to LP Input BTU h Kit Front Part Rear Part Minimum Maximum 30005154 69 029 30000513 54 055 30000514 20 000 28 000 Table ...

Page 30: ...d especially for use on porcelain enamel surfaces Cleaning the Glass WARNING Allow the glass cool completely before attempting to clean ST1125 remove front ST1125 Fig 57 Remove the stove front WARNING HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS 3 Carefully remove the glass and frame assembly and place it out of the way on a flat padded surface suc...

Page 31: ...k into the steel frame Pinch the rounded inside facing gasket material to bulk it up 5 Replace the glass frame and front panel as previously described Inspect the Vent System Annually Have the vent system inspected annually by a qualified technician Shut off the main gas supply before inspect ing the system Both the inner exhaust pipe and the outer combustion supply pipe must be checked to confirm...

Page 32: ...circuit NOTE IF ANY OF THE ORIGINAL WIRE AS SUP PLIED WITH THE APPLIANCE MUST BE RE PLACED IT MUST BE REPLACED WITH TYPE SF 2 200 WIRE OR ITS EQUIVALENT Thermocouple Safety Limit Switch Valve ST665 Safety Limit Switch wiring 5 29 01 djt ST665 Fig 62 Draft hood adapter wiring FAN JUNCTION BOX FAN POWER CORD Strain Relief Chassis Ground BLK GRN GRN WHT ON OFF Rheostat Chassis Ground RHEOSTAT SNAPSTA...

Page 33: ...changes in design materials specifications prices and discontinue colors and products at any time without notice Oxford Direct Vent Natural Vent Gas Heater Models OXDV30NV Ref Description Oxford 1 Gas Log Assembly SDV30 20003458 1a Rear Log 20003459 1b Right Log 20003460 1c Left Log 20003461 2 Small Lava Rock Package 57897 3 Top 30001925 4 Front 30001928 5 Door 30001929 6 End Rt 30001927 7 End Lt ...

Page 34: ...bly NG LP 20002214 22 Grate Burner JDV 20002167 23 Ashdoor Handle Assy E V WSI 5004241 24 Handle Damper Maple Wood Blk 1600664 25 Switch ON OFF RN RP Models 30000874 26 Wiring Harness FSDV32 RN JDV 10002582 27 Right Log Bracket 20002166 28 Left Log Bracket 20002165 29 Nut Hex Jam 3 8 16 TOPLK Z 1203290 30 Gasket Base Pan JDV 20002282 31 Gasket Base Pan Inner 20002566 32 Gasket Cement 3 oz tube not...

Page 35: ... itself does not require regular maintenance how ever periodic cleaning of the fan and the surrounding area is required Installation Refer to Page 14 for installation instructions Remote Controls The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 32 for wiring diagrams Model Functions Controlled RC1 ON OFF RC2 ON OFF and Temperature IMTFK Wall mounte...

Page 36: ...36 Oxford Direct Vent Natural Vent Gas Heater 30005123 ...

Page 37: ...37 Oxford Direct Vent Natural Vent Gas Heater 30005123 ...

Page 38: ...38 Oxford Direct Vent Natural Vent Gas Heater 30005123 ...

Page 39: ...Dealer in home travel fees or service charges for in home repair work It is the dealers option whether the repair work will be done in the customer s home or in the dealer s shop If upon inspection the damage is found to be the fault of the manu facturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this war ra...

Page 40: ...gs Fireplace Efficiency OXDV30NV 63 0 OXDV30PV 63 0 Nous recommandons que nos appareils de chauffage au gaz soient installés et entretenus par des professionnels qui ont été accrédités aux È U par le National Fireplace Institute NFI comme étant des spécialistes du NFI en matièred appareils de chauffage au gaz Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcastingsgroup ...

Reviews: