17
Oxford Direct Vent / Natural Vent Gas Heater
30005123
For DuraVent pipe only:
Install vent pipe by aligning the
locking system together, sliding the pipes together and
twisting clockwise.
• Install 90° elbow. Twist lock as before.
• Slide the wall plate over horizontal run before attach-
ing the horizontal run to the elbow. Fasten wall plate to
wall.
4. For Vermont Castings Group Vent Pipe only:
If nec-
essary, measure to determine the vertical length (X) of
pipe required from the adapter pipe to the wall cutout
centerline, including a 2” (51mm) overlap at the joint.
(Fig. 24) use a hacksaw or tin snips to trim the pipe as
needed.
x
ST764
DW
measure vertical vent
5/15/03 djt
ST764
Fig. 24
Determine the vertical pipe length.
5. Install first the inner then the outer straight pipe
section(s), trimmed end down, to the point of the el-
bow. Drill 3 holes through each joint and fasten with
sheet metal screws.
6. Seal and install the elbow using 3 sheet metal screws
at each joint.
7. Measure, and cut if needed, the appropriate length of
pipe section needed to make the connection through
the wall. Include a 2” overlap; i.e. from the elbow to
the outside wall face, about 2” or the distance required
if installing a second 90° elbow. (Fig. 25)
8. Slip the wall plate and trim collar over the interior end
of the horizontal pipe and install into the wall sleeve.
Seal the joint inside the wall plate if needed to keep
cold air from being drawn into the home.
9. Seal the ends and connect the horizontal pipe to the
elbow. Fasten the wall plate to the pipe with three
sheet metal screws. Slide the trim collar up against
the wall plate to cover the screws. (Fig. 26)
ST215
measure thru wall
12/6/99 djt
ST215
x
Fig. 25
Measure the horizontal length.
ST216
install pipe thru wall
12/6/99 djt
Trim Collar
Wall
Sleeve
Wall Plate
ST216
Fig. 26
Install the horizontal pipe and wall plate parts.
10. For both Vermont Castings Group and DuraVent
Systems:
Install the vent terminal. (Fig. 27) Apply
high temperature sealant one inch from the ends of
the inner and outer collars. Guide the inner and outer
vent termination collars into the adjacent pipes. Dou-
ble check that the vent pipes overlap the collars by 2”.
Fasten the termination to the wall with the screws pro-
vided, and caulk the joint with weatherproof sealant.
11. For Vermont Castings Group only:
Install Charcoal
Gray Pipe Rings (#7FSDRG) or Polished Brass Pipe
Rings (#7FSDRP) at pipe joints, if desired.
ST217
install wall terminal
12/6/99 djt
Seal Both
Terminal Ends
Caulk Plate Joint with
Weatherproof Sealant
ST217
Fig. 27
Install the vent terminal.