INSTALLATIoN GUIDe

WIrIng

  

Power must be disconnected and locked out before making any wiring connections.

Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 9 and 10).

Figure 9

Figure 10

SHIELD
RX- TX- 
RX+ TX+ 
TX-
TX+

Master or Slave

SHLD

TX+  

TX+

RX+

TX–

TX-

RX-

SHIELD

SHIELD

Master 

Slave

SHLD

TX+  

TX+

RX+

TX–

TX-

RX-

SHIELD

SHLD

TX+  

TX+

RX+

TX–

TX-

RX-

SHIELD

2-Wire

4-Wire

2-Wire Example

Figure 11

+

Belden 1120A or 

equivalent

120 

Ω

 terminator 

on last device of 

daisy chain

Not Used

WARNING:  After wiring the RS-485 cable, remove all 

scraps of wire or foil shield from the electrical panel. 

Wire scraps coming into contact with high voltage 

conductors could be DANGEROUS!

+

 

 

1.  Mechanically secure the RS-485 cable where it enters the electrical panel.

2.  Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the 

chain (Figure 11).

3.  Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. The cable 

must  be voltage-rated for the installation.

4.  When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6 

N·m (0.37 to 0.44 ft·lb ) for connectors on main board, 0.22 to 0.26 N·m (0.16 to 
0.19 ft·lb) for connectors on adapter boards (Figure 12).

Figure 12

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Reviews: