background image

Z204998-0M 

PAGE 3 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

e30

INSTALLATIoN GUIDe

data outPut

Monitoring at Mains

E30A

E30B

E30C

Current per phase

Max. current per phase

Current demand per phase

Max. current demand per phase

Energy (kWh) per phase

Real Power (kW) per phase

Apparent Power (kVA)

Power factor total *

Power factor per phase

Voltage - L-L and average

Voltage - L-N and average

Frequency (phase A)

Monitoring at Branch Circuit

Current

Max. current

Current demand

Max. current demand

Real power (kW)

Real power (kW) demand

Real power (kW) demand max.

Energy (kWh) per circuit

Power factor

Apparent  Power (kVA)

Modbus Alarms

Voltage over/under

Current over/under

* Based on a 3-phase breaker rotation.

blInk codes for status led

Color and Pattern

Status Description

Green, once per second

Normal operation

Amber, once per second

Volts or Amps clipping

Amber, twice per second

Invalid firmware image

Amber, three per second

Incorrect strips or strip order

Red, solid or blink

Diagnostic event detected

solId-core ct accuracy

100A Solid-Core CT

Voltage Rating

300 VAC

Accuracy

±0.5%

Temperature

0° to 60°C

Agency

UL508 recognized, EN61010

Product dIagram

7

1

2

3

4

5

6

2

8

9

10

A

A

B

B

11

    

1.  

50-Pin Ribbon Cable Connectors (Data Acquisition Board):

  48-inch (1220 

mm) ribbon cables are provided for easy connection of current sensor strips to 
this point of the data acquisition board. The two connectors on the left are for 
panelboard 1; the two on the right are for panelboard 2. 

Note:  Connect CT strips to the correct ribbon cable connectors for each panel. 
The top connector is for Strip A, and the bottom conector is for Strip B.

Verify that the serial numbers on the CT strips match the serial number 
on the main circuit board (Data Acquisition Board).

2.  

Auxiliary Inputs:

  These 0.333 VAC inputs are used for monitoring the main 

breaker or other high amperage source. Inputs on the left are for panelboard 1; 
inputs on the right are for panelboard 2.

3.  

Control (Mains) Power Connection:

  Easy 2-wire 90-277 VAC 50/60 Hz 

connection.

4.  

Control Power Fuse:

  600 VAC, 500 mA time lag, factory-replaceable.

5.  

Alive LED:

  Red/green/amber LEDs. Blink codes are on page 3.

6.  

Voltage Taps:

  1, 2, or 3 phase plus neutral connections. For voltage sensing and 

power calculations (no voltage taps on the E30C).

7.  

Communications Address DIP Switches:

  Each Modbus device must have a 

unique address. Switches are binary weighted. Left-most switch has a value of 1; 
right-most switch has a value of 128. Note:  the 4-strip model uses 2 addresses.

8.  

Communications Settings DIP Switch:

  Configures baud rate, parity, 2/4 wire 

communications.

9.  

RS-485 2 Connection:

  Used for Modbus serial communications. The Universal 

plug accomodates 2 or 4 wire connections. 

10. 

RS-485 LEDs:

  The RX LED (closest to DIP switches) indicates the RS-485 

is receiving information; the TX LED (farthest from DIP switches) indicates 
transmission of information.

11. 

Power LED:

  Indicates power to main board

12. 

Current Sensors:

  Each current sensor is capable of monitoring conductors rated 

up to a maximum of 100 amps. 

13. 

50 Pin Ribbon Cable Connectors (Current Sensor Strips):

  Connects current 

signal from the sensor strip to the main board via the ribbon connectors.

12

13

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...