e30

INSTALLATIoN GUIDe

troubleshootIng

Problem

Solution

Product is not communicating over Modbus daisy chain

  Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.

  Check Parity.

  Check the communications wiring.

  Check that the daisy chain is properly terminated.

RX LED is solid

  Check for reversed polarity on Modbus comms.

  Check for sufficient biasing on the Modbus bus. Modbus physical specification calls for 450-650 Ω biasing. This is 

usually provided by the master.

The main board has a fast flashing amber light

  Check that the 1A and 1B CT strips are connected to the left top and left bottom ribbon cable connections; 2A and 2B 

must be connected to the right top and right bottom ribbon cable connections (see illustrations in the product install).

  Verify ribbon cable connectors are inserted in the correct orientation.

  If cables are correct, reset main board to re-initialize product.

  Verify serial number on strips matches serial number on main board.

The main board has a slow flashing amber light

  One or more channels is clipping. This can be caused by a signal greater than 100 A or 277 V L-N, or by a signal with 

high THD near the gain stage switching points (1.5 A and 10 A).

The main board has a flashing green light

  Everything is wired properly and the main board has power.

The main board is a flashing or solid red light

  Light may be red briefly while device powers up.

  If light is red for more the 60 sec. device has encountered a diagnostic event. Contact technical support.

Power factor reading is not as expected

  Verify voltage taps are connected in appropriate phase rotation.

  Verify strip configuration register matches actual strip installation.

  Verify phase rotation of breakers (firmware rev. 1.012 or higher allows for custom rotation if needed).

Current reading is not as expected, or reading is on different CT 

number than expected

  Verify strip configuration register matches actual strip installation.

  Verify ribbon cable is fully seated and in the correct orientation.

Current is reading zero, even when small currents are still flowing 

through circuit

  The product cuts off at 50 mA, and will set the reporting register to 0 mA for currents near or below this range.

E3x Config Tool returns Modbus error on read/write

  Verify using the latest release of E3x Config Tool as older versions may not support all features in current product 

firmware. Latest version is available on our website http://www.veris.com/modbus.aspx

chIna rohs comPlIance InformatIon (efuP table)

部件名称 

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板 

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Reviews: