INSTALLATIoN GUIDe

oPeratIon

The E30 Series Branch Current Monitor is a device designed to measure the current, 
voltage, and energy consumption of up to 92 circuits (84 branch circuits, 2 3-phase 
mains, 2 neutrals) on a single board. It increases the board’s current monitoring 
capability by combining the functions of two boards into one device. 

The E30 consists of a data acquisition board and up to four 21-unit current sensor 
strips, with eight auxiliary inputs. The strips are mounted on each side of the panel 
board along the termination points of each breaker. The conductor passes through 
the appropriate current sensor before terminating at the breaker. Each strip transmits 
the current data to the data acquisition board. 

Data is transmitted using an RS-485 Modbus protocol. Each data acquisition board 
requires two addresses, one for each set of two current sensor strips and four 
auxiliary inputs. Data is updated roughly every two seconds. As a circuit approaches 
the user-defined threshold, the E30 activates the alarm indicators.

The E30A measures both current and power for the mains and branch circuits. The 
E30B measures both current and power for the mains, and current only in each circuit. 
The E30C measures current only for the mains and branch circuits.

dImensIons

Circuit Board and Mounting Bracket

7.3”

(184 mm)

8.9”

(288 mm)

5.8”

(146 mm)

4.8”

(122 mm)

3.9”

(100 mm)

7.9”

(200 mm)

8.3”

(211 mm)

1.75”

(45 mm)

Ø = 0.2”

(5 mm)

Solid-Core CT Strips

            

0.4” (10mm) 

opening

1.0” (26mm)

on center

25.0” (635mm)

1.2” 

(31mm)

20.3” (516mm)

1.1” 

(28mm)

0.4” (10mm) 

opening

0.75” (19mm)

on center

0.8” 

(20mm)

1.3” 

(33mm)

2.0” 

(50mm)

slot:  0.25” x 0.5” 

(7 x 13mm)

2.0” 

(50mm)

slot:  0.25” x 0.5” 

(7 x 13mm)

1.2” 

(30mm)

3/4” option

1” option

quIck Install

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1.  Disconnect and lock out power. Use a properly rated voltage sensing device to 

confirm power is off.

2.  Mount current sensor strips adjacent to breaker terminations.

3.  

Verify that the serial numbers on the CT strips match the serial number 

on main circuit board (Data Acquisition Board).

4.  Configure communication and addressing parameters using DIP switches.

5.  Mount the main acquisition board in the electrical enclosure.

6.  Connect current sensor strip cables to the main board, observing the 2-strip or 

4-strip setup and their orientation (A or B) within the panel.

7.  Wire RS-485 communications.

8.  Connect CTs to the auxiliary inputs and connect them onto the main conductors in 

the enclosure (optional).

9.  Wire control power and voltage taps (E30A and E30B only).

10. Download the free E3x configuration tool from www.veris.com to commission the 

device for operation.

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Reviews: