Veris E30 series Installation Manual Download Page 6

Z204998-0M 

PAGE 6 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

07121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

e30

INSTALLATIoN GUIDe

Figure 8

V1       V2         V3         N

V2/N

V1

90-277 VAC

L - L

L - N

Line to Line (L-L) Voltage:  150 to 480 VAC

Line to Neutral (L-N) voltage:  90 to 277 VAC

Voltage taps are shared by both panels.

Figure 6

Figure 7

Set up Modbus registers 115-118 for CT scaling.

Use base + 1 address for Panel 2 setup.

I1
I2 
I3
IN

 I1
 I2
 I3

IN

±
±
±
±

±

±

±

±

Panel 2

Panel 1

CT Input

(0-0.333 VAC)

CT Input

(0-0.333 VAC)

E30 CURRENT SENSOR STRIP

E30 CURRENT SENSOR STRIP

E30 CURRENT SENSOR STRIP

E30 CURRENT SENSOR STRIP

Panel 1

Panel 2

Recommended CT: 

Veris Industries H6810, H6811, H6812 Series with 0.333VAC output.

Available in 100A max. to 2400A max. 

Call a Veris sales rep if higher amperages are required.

7.  Wire RS-485 communications (see diagrams in Wiring section).

8.  Connect 0.333VAC CTs to the main conductors by snapping CTs around lines, 

observing local codes regarding bending radius (optional; Figure 6). 

9.  Connect 2-wire 90-277VAC power to main power terminals. Observe polarity. For 

the E30A and E30B, connect voltage lines to the voltage taps (Figure 8). Equip 
voltage lines with fuses.

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...