background image

ZEC410 VAV Controllers Installation Instructions

17

Occupancy Sensor

All zone controllers support an occupancy sensor. The occupancy sensor enables the controller to switch to 
standby mode from occupied mode when local activity is absent during a set time period in a normally occupied 
zone. When in standby mode, the zone controller uses standby temperature setpoints that are higher and lower 
than the occupied cooling and occupied heating temperature setpoints, respectively. These standby setpoints help 
save energy by reducing the demand for heating and cooling in an unoccupied zone. For VAV zone dampers, the 
sensor uses unoccupied flow setpoints in addition to standby temperature setpoints. You can enable the occupancy 
sensor in the Zone Setup screen of the System Manager or Zone Coordinator.

 

You can set occupancy sensitivity 

and time delay until standby locally at the sensor. Refer to the 

Verasys System User’s Guide (LIT-12012371)

 

for 

more information.

CO

Demand Controlled Ventilation (DCV)

CO

2

 DCV ensures high Indoor Air Quality (IAQ) for the zone by using up to four wall-mounted CO

2

 sensors to 

monitor CO

2

 levels. The sensor measures CO

2

 levels on a scale of 0 to 2,000 parts per million (ppm). When the 

CO

2

 sensor with the highest CO

2

 reading detects that CO

2

 levels in the zone are above the setpoint (such as 

caused by a high number of occupants within the zone), the zone damper opens, to allow more outside air into the 
zone. Enable CO

2

 DCV in the Zone Setup screen of the System Manager or Zone Coordinator. Refer to the

 

Verasys System User’s Guide (LIT-12012371)

 

for more information.

Troubleshooting

Use the following information to troubleshoot the ZEC controllers.

Power Status LED

A green LED shows the power supply status to the VAV zone damper controller. See Table 4 for a description of the 
modes. 

Table 4:  Status LED for Power (PWR)

Mode

Description

Off

No Power

On

Power is supplied by Primary Voltage (Normal operation)

Summary of Contents for ZEC410

Page 1: ...ol system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the ZEC410 VAV contro...

Page 2: ...ven surface whenever possible Use shims or washers to mount the ZEC securely and evenly on the mounting surface if necessary Mount the ZEC in an area free of corrosive vapors that matches the ambient...

Page 3: ...it against the spacer 6 Locate the damper position using the typical marking on the end of the damper shaft Table 1 Verasys System Bus Controller Addressing System Bus Address Range Standalone Verasys...

Page 4: ...d stop the closed end stop is set by the closed damper For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the ZEC controller at the full o...

Page 5: ...op ration de r glage Veiller ne toucher aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles IMPORTA...

Page 6: ...modular SA Bus ports provide a connection for the VAV Balancing Tool The FC Bus port is not used in ZEC installations Figure 3 SA Bus Terminal Block Wiring Stranded 4 Wire 2 Twisted Pair Shielded Cab...

Page 7: ...remental outputs for the heating control 2 Wire the network temperature sensor and CO2 sensor to the ZEC s SA Bus 3 Wire the FC Bus in a daisy chain 4 Ensure that the ZEC s device address DIP switches...

Page 8: ...ZEC410 1 SUPHTG1 C Optional ZN T SA DA ZN CO2 Optional OCC S Optional DA T Optional HTG3 C Optional HTG2 C Optional E C HTG1 C Optional SF C SUPHTG1 C Optional ZN T SA RA DA ZN CO2 Optional OCC S Opt...

Page 9: ...TAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FRO M LAST DEVICE MS TP MS TP Oc cupancy Sensor O LS 2100 1 CONNECTOR O N BACK OF SENSOR ZONE SENSOR ZN CO2 24V HOT COM SA PWR 24V COM SEE RIS...

Page 10: ...e zone temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network un...

Page 11: ...ECTOR ON BACK OF SENSOR ZONE SENSOR ZN T IF NETSTAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FROM LAST DEVICE MS TP MS TP TO RE D WIRE OCCUP ANCY S WITCH TO BLACK WIRE OCCUP ANCY S WITCH...

Page 12: ...ne temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network unit e...

Page 13: ...ONNECTTOAIR FLOWPROBE SF C OPTIONAL DA T DISCHARGEAIRTEMP OPTIONAL 24VHot 24VCom NOTE SUPPLEMENTALVALVESDEFAULTTOA 60 SECONDINCREMENTALACTUATOR THISIS ADJUSTABLEINVERASYS SUPHTG O OPTIONAL CW CCW COM...

Page 14: ...rily sets the VAV box to Standby mode when the occupancy is not sensed When the box senses occupancy the zone switches back to occupied Standby mode uses standby temperature setpoints that are slightl...

Page 15: ...than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switc...

Page 16: ...erature sensor 1k ohm nickel with temperature occupancy button TE 68NT 1N00S Wall temperature sensor 1k ohm nickel with warmer cooler W C adjustment and temperature occupancy pushbutton Zone CO2 Senso...

Page 17: ...cally at the sensor Refer to the Verasys System User s Guide LIT 12012371 for more information CO2 Demand Controlled Ventilation DCV CO2 DCV ensures high Indoor Air Quality IAQ for the zone by using u...

Page 18: ...f the bus for testing purposes and test the bus portion connected to the Zone Coordinator Correcting Physical Communication Bus Problems The communication bus is subject to a number of physical factor...

Page 19: ...50 to 60 Hz Class 2 power supply or Safety Extra Low Voltage SELV at 50 60 Hz 20 VAC minimum Power Consumption 10 VA 14 VA maximum Ambient Conditions Ambient Operating Conditions 0 to 50 C 32 to 122 F...

Reviews: