background image

ZEC410 VAV Controllers Installation Instructions

15

Refer to the 

MS/TP Communications Bus Technical Bulletin (LIT-12011670) 

for detailed information regarding 

wire size and cable length requirements for the Zone Bus.

Wire Gauges and Lengths

Table 2 outlines the VAV controller wiring details.  

Setup and Adjustments

Setting the Device Address

ZEC controllers are master devices on  BACnet® MS/TP (SA or FC) Buses. Before operating  field controllers on a 
bus, you must set a valid and unique  device address for each controller on the bus.

You set a field controller’s device address by setting the  positions of the switches on the Device Address DIP switch 
block at the top of the controller. Device  addresses 4 through 127 are the valid addresses for the ZEC controller.

Note:

ZEC controllers ship with all address switches set to ON. Set a valid and unique device address on the field 

controller before applying power to the controller on the bus.

The DIP switch block has eight switches  numbered 128, 64, 32, 16, 8, 4, 2, and 1. 

To set the device addresses on a ZEC field controller:

1.

Set all of the switches on the field controller’s device  address DIP switch block (128 through 1) to OFF.

2.

Set one or more of the six address switches (32 through 1) to ON, so that the sum of the switch numbers set to 
ON equals the intended device address. 

Set the highest number switch that is less than or equal to the intended device address to ON. Then continue 
setting lower numbered switches until the total equals the intended address. For example, if the intended device 
address is 21, set Switch 16 to ON first, then set Switch 4 ON, followed by Switch 1 (16+4+1=21). 

3.

Set a unique and sequential device address for each of the field controllers connected on the System Bus or 
Zone Bus, starting with device address 6.

Table 2:  ZEC Controller Wiring

Terminal

Terminal Labels

Function and Electrical Ratings/
Requirements

Recommended Cable Type 
and Length

Analog Input 
(AI)

IN1

Provides an AI connection for discharge 
air (DA-T) sensor

0.6 mm (22 AWG) stranded, 
2-wire twisted cable 
recommended for runs of <30 m 
(90 ft).

IN2

Provides a BI connection for occupancy 
sensor dry contact (optional)

N/A

Binary Output 
(BO)

(Integrated)

Provides a BO connection for clockwise 
(CW) rotation to (Open) of actuator, 24 
VAC triac output.

N/A

(Integrated)

Provides a BO connection for 
counterclockwise (CCW) rotation to 
(Close) of actuator, 24 VAC triac output.

N/A

Sensor Actuator 
(SA) Bus 
Terminal Block

+, -, COM, PWR

Sources 15 VDC power for SA Bus 
devices; supports 5 NS Series Network 
Zone Temperature

 

Sensors and up to 5 

NS Series Network CO

2

 Sensors.

0.6 mm (22 AWG) stranded, 
4-wire twisted cable 
recommended for runs of <30 m 
(99 ft)

FC Bus Terminal 
Block

+ - Com

Provides communication network

0.65 mm (22 AWG) stranded, 
twisted shielded cable 
recommended for runs of 1,000 
feet maximum

24 VAC Power

Hot

AC supply input supply 20–30 VAC 
(Nominal 24 VAC)

0.8 mm to 1.5 mm 
(20 to 16 AWG) 2-wire

Com

24 VAC power common

Summary of Contents for ZEC410

Page 1: ...ol system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the ZEC410 VAV contro...

Page 2: ...ven surface whenever possible Use shims or washers to mount the ZEC securely and evenly on the mounting surface if necessary Mount the ZEC in an area free of corrosive vapors that matches the ambient...

Page 3: ...it against the spacer 6 Locate the damper position using the typical marking on the end of the damper shaft Table 1 Verasys System Bus Controller Addressing System Bus Address Range Standalone Verasys...

Page 4: ...d stop the closed end stop is set by the closed damper For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the ZEC controller at the full o...

Page 5: ...op ration de r glage Veiller ne toucher aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles IMPORTA...

Page 6: ...modular SA Bus ports provide a connection for the VAV Balancing Tool The FC Bus port is not used in ZEC installations Figure 3 SA Bus Terminal Block Wiring Stranded 4 Wire 2 Twisted Pair Shielded Cab...

Page 7: ...remental outputs for the heating control 2 Wire the network temperature sensor and CO2 sensor to the ZEC s SA Bus 3 Wire the FC Bus in a daisy chain 4 Ensure that the ZEC s device address DIP switches...

Page 8: ...ZEC410 1 SUPHTG1 C Optional ZN T SA DA ZN CO2 Optional OCC S Optional DA T Optional HTG3 C Optional HTG2 C Optional E C HTG1 C Optional SF C SUPHTG1 C Optional ZN T SA RA DA ZN CO2 Optional OCC S Opt...

Page 9: ...TAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FRO M LAST DEVICE MS TP MS TP Oc cupancy Sensor O LS 2100 1 CONNECTOR O N BACK OF SENSOR ZONE SENSOR ZN CO2 24V HOT COM SA PWR 24V COM SEE RIS...

Page 10: ...e zone temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network un...

Page 11: ...ECTOR ON BACK OF SENSOR ZONE SENSOR ZN T IF NETSTAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FROM LAST DEVICE MS TP MS TP TO RE D WIRE OCCUP ANCY S WITCH TO BLACK WIRE OCCUP ANCY S WITCH...

Page 12: ...ne temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network unit e...

Page 13: ...ONNECTTOAIR FLOWPROBE SF C OPTIONAL DA T DISCHARGEAIRTEMP OPTIONAL 24VHot 24VCom NOTE SUPPLEMENTALVALVESDEFAULTTOA 60 SECONDINCREMENTALACTUATOR THISIS ADJUSTABLEINVERASYS SUPHTG O OPTIONAL CW CCW COM...

Page 14: ...rily sets the VAV box to Standby mode when the occupancy is not sensed When the box senses occupancy the zone switches back to occupied Standby mode uses standby temperature setpoints that are slightl...

Page 15: ...than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switc...

Page 16: ...erature sensor 1k ohm nickel with temperature occupancy button TE 68NT 1N00S Wall temperature sensor 1k ohm nickel with warmer cooler W C adjustment and temperature occupancy pushbutton Zone CO2 Senso...

Page 17: ...cally at the sensor Refer to the Verasys System User s Guide LIT 12012371 for more information CO2 Demand Controlled Ventilation DCV CO2 DCV ensures high Indoor Air Quality IAQ for the zone by using u...

Page 18: ...f the bus for testing purposes and test the bus portion connected to the Zone Coordinator Correcting Physical Communication Bus Problems The communication bus is subject to a number of physical factor...

Page 19: ...50 to 60 Hz Class 2 power supply or Safety Extra Low Voltage SELV at 50 60 Hz 20 VAC minimum Power Consumption 10 VA 14 VA maximum Ambient Conditions Ambient Operating Conditions 0 to 50 C 32 to 122 F...

Reviews: