ZEC410 VAV Controllers Installation Instructions

10

Sequence of Operation for Staged with Reheat Control

Occupied Mode:

 When the zone temperature is between the occupied heating and cooling setpoints (inside of the 

bias), the primary air damper is at the Minimum CFM and no mechanical heating runs. When the zone temperature 
rises above the cooling setpoint, the primary air damper increases the cfm and no mechanical heating runs. If a 
drop in zone temperature below the heating setpoint occurs, the supplemental heating coil is fully used before the 
reheat heat coil enables, and the damper opens to provide to minimum cfm.

Note:

The box reheat and supplemental reheat is a box option. You have a cooling only box if you do not select 

either reheat or supplemental reheat. 

Unoccupied Mode: 

In unoccupied mode, when the zone temperature is between the unoccupied heating and 

cooling setpoints (inside of the bias), the primary air damper is at the minimum cfm and no mechanical heating 
runs. When the zone temperature rises above the unoccupied cooling setpoint, the primary air damper increases 
the cfm (if available), and no mechanical heating runs. When the zone temperature drops below the unoccupied 
heating setpoint, the supplemental heating coil is fully used before the reheat heat coil enables. The damper is at 
the minimum cfm.

Unit Enable: 

A network unit enable signal controls the mode of the box.

Fan Control (Optional): 

With parallel fans, when a call for heat occurs, the fan cycles on. In all other states the fan 

remains off. With series fans, in occupied mode, the fan runs continuously. In unoccupied mode, the fan cycles on 
with a call for heating or cooling.

Occupancy Lighting Switch (Optional): 

You can add an occupancy lighting switch to the box, temporarily setting 

the VAV box to Standby mode when the occupancy is not sensed. When the box senses occupancy, the zone 
switches back to occupied. Standby mode uses standby temperature setpoints that are slightly highter or lower 
than the occupied cooling or heating setpoints, respectively. The VAV box also uses unoccupied flow setpoints in 
addition to the low temperatures.

Demand Control Ventilation (Optional): 

When zone CO

2

 sensors are wired to the boxes to sense the air quality 

in the zone, the minimum damper flows are proportionally reset based on an air quality setpoint (CO

2

). The reset of 

the damper minimum flows do not exceed the maximum value that you set. the CO

sensor with the highest value 

determines the reset, if more than one is wired.

Summary of Contents for ZEC410

Page 1: ...ol system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the ZEC410 VAV contro...

Page 2: ...ven surface whenever possible Use shims or washers to mount the ZEC securely and evenly on the mounting surface if necessary Mount the ZEC in an area free of corrosive vapors that matches the ambient...

Page 3: ...it against the spacer 6 Locate the damper position using the typical marking on the end of the damper shaft Table 1 Verasys System Bus Controller Addressing System Bus Address Range Standalone Verasys...

Page 4: ...d stop the closed end stop is set by the closed damper For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the ZEC controller at the full o...

Page 5: ...op ration de r glage Veiller ne toucher aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles IMPORTA...

Page 6: ...modular SA Bus ports provide a connection for the VAV Balancing Tool The FC Bus port is not used in ZEC installations Figure 3 SA Bus Terminal Block Wiring Stranded 4 Wire 2 Twisted Pair Shielded Cab...

Page 7: ...remental outputs for the heating control 2 Wire the network temperature sensor and CO2 sensor to the ZEC s SA Bus 3 Wire the FC Bus in a daisy chain 4 Ensure that the ZEC s device address DIP switches...

Page 8: ...ZEC410 1 SUPHTG1 C Optional ZN T SA DA ZN CO2 Optional OCC S Optional DA T Optional HTG3 C Optional HTG2 C Optional E C HTG1 C Optional SF C SUPHTG1 C Optional ZN T SA RA DA ZN CO2 Optional OCC S Opt...

Page 9: ...TAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FRO M LAST DEVICE MS TP MS TP Oc cupancy Sensor O LS 2100 1 CONNECTOR O N BACK OF SENSOR ZONE SENSOR ZN CO2 24V HOT COM SA PWR 24V COM SEE RIS...

Page 10: ...e zone temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network un...

Page 11: ...ECTOR ON BACK OF SENSOR ZONE SENSOR ZN T IF NETSTAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FROM LAST DEVICE MS TP MS TP TO RE D WIRE OCCUP ANCY S WITCH TO BLACK WIRE OCCUP ANCY S WITCH...

Page 12: ...ne temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network unit e...

Page 13: ...ONNECTTOAIR FLOWPROBE SF C OPTIONAL DA T DISCHARGEAIRTEMP OPTIONAL 24VHot 24VCom NOTE SUPPLEMENTALVALVESDEFAULTTOA 60 SECONDINCREMENTALACTUATOR THISIS ADJUSTABLEINVERASYS SUPHTG O OPTIONAL CW CCW COM...

Page 14: ...rily sets the VAV box to Standby mode when the occupancy is not sensed When the box senses occupancy the zone switches back to occupied Standby mode uses standby temperature setpoints that are slightl...

Page 15: ...than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switc...

Page 16: ...erature sensor 1k ohm nickel with temperature occupancy button TE 68NT 1N00S Wall temperature sensor 1k ohm nickel with warmer cooler W C adjustment and temperature occupancy pushbutton Zone CO2 Senso...

Page 17: ...cally at the sensor Refer to the Verasys System User s Guide LIT 12012371 for more information CO2 Demand Controlled Ventilation DCV CO2 DCV ensures high Indoor Air Quality IAQ for the zone by using u...

Page 18: ...f the bus for testing purposes and test the bus portion connected to the Zone Coordinator Correcting Physical Communication Bus Problems The communication bus is subject to a number of physical factor...

Page 19: ...50 to 60 Hz Class 2 power supply or Safety Extra Low Voltage SELV at 50 60 Hz 20 VAC minimum Power Consumption 10 VA 14 VA maximum Ambient Conditions Ambient Operating Conditions 0 to 50 C 32 to 122 F...

Reviews: