English
[OUT] output menu
Confi gurable
Parameter
parameter
Description
unit
value default notes
labels
min
max
ETR
relay
time-
control activation
-
0
0
3
(5)
DON
minimum
time
between
2 starts of same relay
min
0
200
0
(6)
TOF
minimum
ON
time
of relay
min
0
200
0
(7)
TON
minimum
OFF
time
of relay
min
0
200
0
(8)
INI
initial
delay
from device start
min
0
200
0
(9)
TCL
PWM
cycle
time
sec
1 200 200 (10)
Note:
(5) this parameter enables the control of times set in DON, TOF, and TON for each
output as follows:
0
timing
disabled
for both relay outputs
1
timing enabled only for relay 1 output
2
timing enabled only for relay 2 output
3
timing enabled for both relay 1 and 2 outputs
(6) this parameter restricts the number of starts per hour for the equipment connected
to the device (parameter frequently used e.g. for compressors)
(7) minimum time in which output must remain ON
(8) minimum time in which output must remain OFF
(9) output activation delay time from reset of the device
(10) the period that can be set for PWM regulation. This reading is displayed only if the
operating mode selected is PRO=5 (see system menu).
[ING] outside input menu
Confi gurable
Parameter
parameter
Description
unit
value default notes
labels
min
max
TID
digital
input
function
-
0 4
0
(11)
DID
digital
input
delay
min
0 200 0
(12)
SUI
output
status
with
dig. input enabled (open)
-
0
3
0
(13)
Note:
(11) Confi gurable values are:
0
disabled
- 42 -
User Manual – Thermoregulator FHT