English
(16) if “yes” both key beep and alarm-condition buzzer are enabled. If “no” both are
disabled
(17) If “yes” the type of alarm is displayed even during timing of the same, if “no” the
type of alarm is displayed only after the timing
(18) if “yes”, at the end of a min/max alarm it will be necessary to dismiss alarm type
reading and reset the relay manually
(19) if “yes”, at the end of a min/max alarm it will be necessary to dismiss alarm type
reading manually (the relay will automatically reset instead)
(20) blocks the generation of max/min alarms for a period
[DSP] view menu
Confi gurable
Parameter
parameter
Description
unit
value default notes
labels
min
max
LO1
lower limit of set-point 1
degrees -99 HI1
-99
HI1
upper limit of set-point 1
degrees LO1 999
999
LO2
lower limit of set-point 2
degrees -99 HI2
-99
(21)
HI2
upper limit of set-point 2
degrees LO2 999
999
(21)
SOF
probe 1 calibration offset
degrees -50 +50
0.0
(22)
SIF
probe 2 calibration offset
degrees -50 +50
0.0
(22)
RIS
reading
resolution
-
HI LO HI
(23)
UNI
temperature measurement unit
-
C
F
C
(24)
FIL
measurement
fi
lter
-
no yes yes (25)
Note:
(21) parameter is active only if it applies to the operating mode
(22) value added to the measure to compensate for an inaccuracy of the same
(23) reading resolution:
0.1 if “HI” or 1.0 if “LO”
(24) Attention: when unit of measurement is changed, parameter settings are not
converted automatically and must be recalibrated.
(25) if the parameter is set to “yes” a moving average of 8 measurement values (i.e. of
about 4 seconds) is calculated, if “no” the average is not calculated
- 44 -
User Manual – Thermoregulator FHT