English
[ANG] analog output menu
Confi gurable
Parameter
parameter
Description
unit
value default notes
labels
min
max
ANT
type of analog output
-
0
2
0
(32)
ALO
value
corresponding
to lower limit
degrees -99 999
00.0
(33)
AHI
value
corresponding
to upper limit
degrees -99 999
100
(33)
Note:
(32)
Analog output
display reading
voltage 0-10 V
0-1
amperage 0-20 mA
020
amperage 4-20 mA
420
(33) it is possible to set an output range with AHI less than ALO to allow the output to
decrease with the increase of the measured parameter
[ADD] special parameters menu
Confi gurable
Parameter
parameter
Description
unit
value default notes
labels
min
max
DP0
output 1 dependency
-
0
10
(34)
TI0
on/off type or PWM 1
-
0
1
(35)
DB0
dead band 1
-
0
1
(36)
IN0
cut-in
1
%
-100
+100
(37)
DF0
logic 1 differential
%
-100 +100
(38)
DP1
output 2 dependency
-
0
10
(34)
TI1
on/off type or PWM 2
-
0
1
(35)
DB1
dead
band
2
-
0 1
(36)
IN1
cut-in
2
%
-100
+100
(37)
DF1
logic 2 differential
%
-100 +100
(38)
Note:
(34) the parameter establishes in what way an output depends on a set-point or alarm
function. The values take on the following meanings:
0
output not active
1
output relative to set-point 1
2
output relative to set-point 2
3
change-over between output in direct (with set-point 1 and differential 1) and
output in reverse (with set-point 2 and differential 2) by means of digital input
(open - direct, closed - reverse).
- 48 -
User Manual – Thermoregulator FHT