To convert this boiler for use on LP
gas, perform the following steps:
1) If not already done, install the boiler in accordance
with this manual, following all instructions in
Section XI “Start-up and Check-out” up to Step 10.
2) Install provided LP gas orifice per Table A. Orifice
installation is shown in Figure A.1. Boiler sizes
205 and 270 require field installation of factory
supplied orifice and adjustment of throttle screw
for conversion to LP gas. Boiler sizes 85, 110, and
155, require only adjustment of throttle screw for
conversion to LP gas.
DANGER
These instructions include a procedure for adjusting the air-fuel mixture on this boiler. This procedure
requires a combustion analyzer to measure the CO2 (or Oxygen) and Carbon Monoxide (CO) levels in flue
gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in unreliable boiler
operation, personal injury, or death due to carbon monoxide poisoning.
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly, a fire, an explosion or production of carbon
monoxide may result causing property damage, personal injury, or loss of life. The qualified service
agency is responsible for proper installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied
with the kit.
Appendix A: Instructions for Conversion of this Boiler for use with LP Gas
Table A: LP Gas (Propane) Orifice Sizes
(Field Installed)
Boiler Size
LP Gas Orifice
Dia.
85
not used
110
not used
155
not used
205
0.224 in.
270
0.224 in.
Figure A.1: LP Orifice Installation
LP ORIFICE
(SIZES 205-270 MBH ONLY)
O-RING
CAUTION
The gas supply shall be shut off prior to disconnecting the electrical power, before proceeding with the
conversion.
Summary of Contents for Raptor RPTR155
Page 1: ...1 ...
Page 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Page 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Page 88: ...88 X Wiring continued ...
Page 97: ...97 Operating Instructions XI Start Up and Checkout continued ...
Page 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Page 172: ...172 ...