Table B.4: Fan Speeds Tested
Appendix B - (continued)
Model Size
No. Counter-Clockwise Turns
(From Fully Closed)
85
2½
110
2½
155
3
205
4½
270
2¼
Table B.5: Starting Number of Throttle Turns for
Conversion to LP Gas
WARNING
All combustion performance numbers MUST be
verified with a combustion analyzer. Failure to
do so will result in substantial property damage,
severe personal injury or death.
Table B.6: LP Gas (Propane) Orifice Sizes
(Field Installed)
Model Size
LP Gas Orifice
Dia.
85
not used
110
not used
155
not used
205
0.224 in.
270
0.224 in.
Model
Fuel
HF Target FS (RPM)
LF Target FS (RPM)
4501-
6000 ft.
6001-
7800 ft.
7801-
10,100 ft.
4501-
6000 ft.
6001-
7800 ft.
7801-
10,100 ft.
RPTR085
NG
6100
6650
7200
1600
1700
1800
LP
6100
7000
7200
1600
1700
1800
RPTR110
NG
6450
6900
7200
1600
1700
1800
LP
6450
6900
7200
1600
1700
1800
RPTR155 &
RPTR155C
NG
6500
7100
7100
1600
1600
1700
LP
6900
7100
7100
1600
1600
1700
RPTR205
NG
7500
6800
6800
1700
1600
1600
LP
8100
7200
6800
1750
1700
1600
RPTR270
NG
7000
6750
6450
1800
1700
1700
LP
8500
6950
6650
2000
1750
1700
Summary of Contents for Raptor RPTR155
Page 1: ...1 ...
Page 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Page 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Page 88: ...88 X Wiring continued ...
Page 97: ...97 Operating Instructions XI Start Up and Checkout continued ...
Page 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Page 172: ...172 ...