28
VII. Venting
C. Design Requirements Unique to Vertical Venting Systems (continued)
Figure 7.12: Snorkel Terminal Configuration (CPVC/PVC Vent Systems Only)
C. Design Requirements Unique to Vertical Venting Systems
Table 7.13a summarizes all vertical twin pipe vent options. Table 7.13.b summarizes vent options in which an abandoned
B-vent chimney is used both as a chase for the vent pipe and as a conduit for combustion air.
In addition to the requirements in Part VII-A, observe the following design requirements:
1. Permitted Terminals for Vertical Venting
Terminal Option H: Fittings (Acceptable for Vent Options 10-17) – Vent terminates in a plain end (coupling for PVC, bell
end for PolyPro, Polyflue and plain end pipe for InnoFlue). Intake terminates in a PVC 180 elbow pointing down (two sweep
90’s may be substituted). Observe the clearances from the roof, and normal snow line on the roof, shown in Figures 7.15 and
7.17. The section of PolyPro, Polyflue or InnoFlue exposed to the outdoors must be UV resistant.
Use of rodent screens is generally recommended for both terminations. Two rodent screens suitable for 3" PVC terminals
are installed as shown in Figure 7.28. If 2" CPVC is used, these screens can be cut to fit into the smaller fittings. Rodent
screens (“bird guards”) for PolyPro, Polyflue and InnoFlue are as follows:
Size/Vent System
Rodent Screen (“Bird Guard”)
2" PolyPro
DuraVent # 2PPS-BG
3" PolyPro
DuraVent # 3PPS-BG
2" Polyflue
Selkirk # 2PF-HVST
3" Polyflue
Selkirk # 3PV-HVST
2" InnoFlue
Centrotherm # IASPP02
3" InnoFlue
Centrotherm # IASPP03
Terminal Option I: Ipex FGV Concentric Terminal (Acceptable for Vent Options 10 & 11) - This terminal is shown in Figure
7.16 and may be used with CPVC/PVC vent systems. Use a compatible roof flashing and storm collar in accordance with
the Ipex instructions for this terminal. This terminal is available in various lengths and in both PVC and CPVC. Terminals
acceptable for use with these vent options are as follows:
Ipex PN
FGV Concentric Terminal Description
196005
2 x 16" PVC
196105
2 x 28" PVC
196125
2 x 40" PVC
196006
3 x 20" PVC
196106
3 x 32" PVC
196116
3 x 44" PVC
197107
3 x 32" CPVC
197117
3 x 44" CPVC
See Part VII-E of this manual and the Ipex instructions provided with the terminal, for installation details.
Summary of Contents for Raptor RPTR155
Page 1: ...1 ...
Page 13: ...13 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Page 87: ...87 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Page 88: ...88 X Wiring continued ...
Page 97: ...97 Operating Instructions XI Start Up and Checkout continued ...
Page 148: ...148 XV Repair Parts continued 6D 6B 6A 6E 6I 6G 6L 6N 6H 6C 6K 6M 6C 6C 6J 6J 6F All Models ...
Page 172: ...172 ...