background image

HAM841K                                                                                                                                                                                               GB 

4

PANIC 
SMOKE/FIRE 
SENSORS 

NOTE :  
N.O. CONTACTS SHOULD 
BE WIRED IN PARALLEL 

1K - 
INTERNAL 

CATHODE 

LED

ANODE 

CATHODE 

SMALL FLAT 

CATHODE 

ANODE 

ALARM SENSOR 
CONTACTS 

NOTE :  
N.C. CONTACTS SHOULD 
BE WIRED IN SERIES 

 

CONNECTIONS 

 
Terminal 1 & 2 : 24 hr instant-alarm circuit 
This circuit is monitored round the clock and is unaffected by the alarm key switch. This is a normally open circuit. It can be 
used for fire and smoke detectors, panic switches and tamper circuits. Note : these two terminals must remain open, i.e. no 
connection should exist between 1 & 2 when all switches and sensors are in their normal reset positions. 
 
 
 
 
 
 
 
 
 
 
 
Terminal 2 & 3 : N.C. Instant-alarm Circuit 
This circuit is controlled by the alarm on/off key switch. Use it to connect any area that requires protection without using a 
delay between detection and the sounding of the siren - motion sensors, window switches, window foil tapes etc. can be 
connected here. The contacts of these sensors should be shorted when in the normal reset condition and they should be 
arranged in a series loop (see figure 2). 
 
 
 
 
 
 
 
 
 
 
 

 

 

FIG. 2 : N.C. INSTANT-ALARM CIRCUIT 

 
Terminal 4 : Alarm status indication 
Terminal 4 allows the connection of a low-current LED with the same function as the Exit/Alarm LED. It can be used on 
external key switches in order to provide an indication of the alarm status. The cathode terminal (normally indicated by a 
small flat on the plastic body adjacent to the lead. The cathode is the shorter of the two leads of this LED) is connected to 
terminal 4 and the anode terminal is connected to the positive power connection (terminal 21). This circuit does not require 
a resistor as the control panel is equipped with an internal resistor. Reverse the connections and try again if the LED does 
not work. LEDs are available from electronic supply stores. 
 
 
 
 
 
 
 
 
 
 
 

 

 

FIG. 3 : REMOTE ALARM STATUS INDICATOR 

FIG.1 : 24HR INSTANT-ALARM CIRCUIT

 

Summary of Contents for HAM841K

Page 1: ...HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL...

Page 2: ...ed by the internal buzzer that beeps 2 seconds on 1 4 second off during the alarm period This switch should be placed in the operate position for the siren and relays to operate normally 3 Duration Si...

Page 3: ...ory LED GREEN This LED will light when the alarm is triggered and will remain lit until the main power switch is turned off or until the key switch is turned off on off The alarm was triggered in your...

Page 4: ...siren motion sensors window switches window foil tapes etc can be connected here The contacts of these sensors should be shorted when in the normal reset condition and they should be arranged in a se...

Page 5: ...under normal circumstances The delay is adjustable from 0 5 sec to 90 seconds by using the control marked entry delay FIG 4 N C DELAYED ALARM CIRCUIT Terminal 6 7 N O Delayed alarm Circuit This circui...

Page 6: ...the 1K ohm resistor installed across the terminals should be left in place if no speaker is connected Remove this resistor if a speaker is connected FIG 7 CONNECTION FOR SPEAKER SIREN Terminal 13 14...

Page 7: ...ut The polarity of these terminals is irrelevant if you have a 16V AC panel Simply connect the two wires from the plug pack to these terminals If you have a 12V DC panel you should be careful to conne...

Page 8: ...ERMINAL FOR SWITCHABLE 12V POWER SOURCE Terminal 20 21 and 8 These terminals are used for remote key switches If no remote key switch is used terminals 20 and 21 should be shorted in order to disable...

Page 9: ...d should be linked in order to charge the battery NOTE When using standard batteries do not link terminals 9 10 to the battery use a 12V rechargeable battery SIREN WILL NOT SOUND Test Operate switch i...

Reviews: