6 Set up with the display and adjustment module
FIBERTRAC 31 • Profibus PA
43833-EN-170126
Menu
Menu item
Default value
Setup
Sensor address
126
Measurement loop name
Sensor
Isotope
Cs-137
Application
Limit level
Background radiation
0 ct/s
Temperature unit
° C
Adjustment mode
1-point
Adjustment (uncovered)
90000 ct/s
Delta I
90 %
AI FB1 Channel
Process value
AI FB1 scaling unit
%
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping
0 s
Mode relay
Dry run protection
Lock adjustment
Released
Display
Language
Selected language
Displayed value
Pulse rate (ct/s)
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
The copied data are permanently saved in an EEPROM memory in
the display and adjustment module and remain there even in case of
a power failure. From there, they can be written into one or more sen
-
sors or kept as backup for a possible sensor exchange.
Note:
Before the data are copied into the sensor, a check is carried out to
determine if the data fit the sensor. If the data do not fit, a fault signal
is triggered. When data are being written into the sensor, the display
shows which instrument type the data originate from and which TAG
number this sensor had.
Info
In this menu you will find the following menu items:
•
Instrument name - shows instrument name and serial number
Additional settings - Copy
instrument settings
Info