6 Set up with the display and adjustment module
FIBERTRAC 31 • Profibus PA
43833-EN-170126
Measured value max.
To damp process-dependent measured value fluctuations, you can
set a time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
In this menu item you can select which mode the sensor should oper
-
ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.
Overfill protection = the relay will deenergise (safe state) when the
max. level is reached.
Dry run protection = the relay will deenergise (safe state) when the
min. level is reached.
Make sure that you have selected the correct characteristics. See
menu item "
Setup/Current output mode
".
In the menu item "
Lock/unlock adjustment
", you can protect the sen-
sor parameters against unauthorized or inadvertent modification. The
sensor is locked/unlocked permanently.
With locked instrument, only the following adjustment functions are
possible without entering a PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod
-
ule.
Before you lock the sensor in unlocked condition, you can modify the
four-digit PIN number.
Setup - AI FB1 - Damping
Setup - Relay
Lock/unlock setup - Ad-
justment